17
TYPE 4
Input of sensors, analogical outlet (0-10 V). The
programme is given a reference, a proportional band
and a maximum and minimum percentage of outlet.
When the value of the sensor is lower than the
reference, the outlet increases proportionally from the
minimum to the maximum, obtaining this last one when
the sensor reaches the value of reference minus the
programmed proportional band.
Example: Proportional heating.
CONSULT
P03 HEAT-1 E 21.5 ºC
S 025%
PROGRAMME
P03 HEAT-1 C0
Reference= 22.0 ºC
Pro. Band= 02.0 ºC
Min= 00% Max= 090%
High alarm(+)= 00.0
Low alarm(-)= 03.8
Manual (Yes/no)= No
CURVE1
P03 HEAT-1 C1Pto1
Pos=000
Ref=34.0 ºC
Pos=017
Ref=26.5 ºC
Pos=035
Ref=23.5 ºC
Pos=045
Ref=22.0 ºC
CURVE2
P03 HEAT-1 C1Pto1
Min=00%
Max=090%
Min=00%
Max=085%
Min=00%
Max=075%
Min=00%
Max=070%
CONFIGURATION
P03 HEAT-1
Type of working= 4
Text= 02
Number= 1
Num. of inputs= 3 0
Num. of outlet= 03
Conditioning Pro.= 00
Affects in code= 00
RECORD
HEAT-1 24/06 (047%)
22.1
21.2
19.7 ºC
High alarm
15.0
VALUE OF
SENSOR
12.5
REFERENCE
10.0
PROPORTIONAL BAND
7.5
Low alarm
5.0
100 %
MAXIMUM
MINIMUM
000 %