82
ELECTRICAL CONNECTIONS
Caution
Electrical compartment contains live terminals, please ensure supply is isolated before
removing the cover. Any person accessing this part of the unit should be suitably trained and
competent.
Before carrying out any maintenance work, disconnect the drive and the external control
circuits from the power supply by moving the main system switch to “off”. Once power has
been disconnected from the drive,
wait at least 5 minutes before disconnecting the
electrical cables.
Product / Compressors
Electrical supply
MAX amperage of
the unit
2 x DY45
400 V / 3 ph / 50Hz
N+G
29.1 A
2 x RY100
36.3 A
3 x RY100
54.5 A
4 x RY100
70.6 A
5 x RY100
86.7 A
4PTE-7K
400 V / 3 ph / 50Hz
N+G
19.4 A
2 x 4PTE-7K
34.7 A
4PTE-7K + 4MTE-10K
43.4 A
2 x 4MTE-10K
50 A
4MTE-10K + 4KTE-10K
50.5 A
2 x 4KTE-10K
67.4 A
2 x 4PTE-7K + 2MME-07K
400 V / 3 ph / 50Hz
N+G
39.8 A
41.2 A
2 x 4PTE-7K + 2KME-1K
4PTE-7K + 4MTE-10K + 2MME-07K
48.5 A
4PTE-7K + 4MTE-10K + 2KME-1K
49.9 A
4PTE-7K + 4MTE-10K + 2JME-2K
48.7 A
2 x 4MTE-10K + 2MME-07K
55.1 A
56.5 A
2 x 4MTE-10K + 2KME-1K
2 x 4MTE-10K + 2JME-2K
55.3 A
2 x 4MTE-10K + 2HME-3K
56.2 A
4MTE-10K + 4KTE-10K + 2MME-07K
55.6 A
4MTE-10K + 4KTE-10K + 2KME-1K
57 A
4MTE-10K + 4KTE-10K + 2JME-2K
55.8 A
4MTE-10K + 4KTE-10K + 2HME-3K
56.7 A
72.5 A
73.9 A
2 x 4KTE-10K + 2MME-07K
2 x 4KTE-10K + 2KME-1K
2 x 4KTE-10K + 2JME-2K
72.7 A
73.6 A
2 x 4KTE-10K + 2HME-3K