NOTICE D’INSTRUCTIONS GENERALE POUR
COFFRETS ET ARMOIRES ELECTRIQUES
V3.0
Page 37 / 51
-
The installer will have to take care about the way to mount and fix the cables for the
disturbing and sensitive devices, for the connections as well as for the tracking.
-
Cables for disturbing and sensitive devices will have to be shielded.
-
The shield will have, if possible, to be connected to the shield connection features,
efficiently (ideally with a connection at 360° on the peripheral face of the shield) by a shield
necklace or a EMC cable gland for example.
-
The connection of the disturbing or sensitive cables will have to maintain a shielded
connection to the earth preferably on both sides of each cable.
-
A shield not connected to the ground and earth can be subject to important voltage level. It
is absolutely prohibited.