3.9 Digital Out Puts
No of Digital Out Puts
6
Out Put drive
To drive Relays
Out Put current
400mA
Out Put polarity
Delivers System Voltage
Protection
Over Temperature, Short Circuit, Over current and Load Dump
3.10 Communication Ports
USB
USB 2.0 Running on PC and can be used to:
• Program the Controller
• Read Instantaneous Parameters
• Read Fault History & Event Recordings
• USB Cable Type A to Type B
CAN
• J1939 Implementation at 250K
• Non-Isolated
• Internal Termination of 120 Ω
• Details on Request
RS485
• Fully Isolated and Protected against 200V between D+ & D-
• Isolation voltage 4KV
• Modbus Implemented
• Protocol on Request
• Internal Termination of 120 Ω
4.0. Salient Features, Measurement, Protection and Supervision
4.1 Salient Features
1. Fully field programmable either from front Keypad, through PC via USB or in field through
Modbus communication
2. Built in sensor data as well as provision to program a sensor data
3. Bright LCD with Icon and English Text Based Descriptions. No need to remember Icons or
consult the manual for understanding the displayed parameters, status, warning or fault
announcement.
4. 4-20mA Pressure Sensor can be interfaced
5. Fuel Solenoid can be configured as Pull to Start or Pull to Stop
6. System Configurable for:
a. Mains Single Phase Mains and Single-Phase Generator
b. Mains Three Phase and Generator Single Phase
c. Mains Three Phase and Generator Three Phase
7. SMPS Power Supply.
8. Heavily protected and isolated Rs485
9. Provision of measuring Fan Current and Protection against Fan failure for water
cooled engines