15.4 Protection Parameter
Fuel Warn
Level
Monitoring value of fuel level below
which fuel level warning is generated.
15
Disabled*
11-80 %
Fuel Warn
Delay
Monitoring time for above.
10
1-100 Sec
Fuel Trip Level Monitoring value of fuel level below
which fuel level trip is generated.
15
10-80 %
Disabled*
Fuel Trip Delay Monitoring time for above.
10
1-100 Sec
LLOP Trip LevelMonitoring value of lube oil pressure
below which LLOP trip is generated.
1.0
0.4-8.5 Kg/cm2
Disabled*
LLOP Trip
Delay
Monitoring time for above.
5
1-100 Sec
HWT Trip LevelMonitoring value of water temperature
above which HET trip is generated.
90
40-249
Disabled*
HWT Trip DelayMonitoring time for above.
5
1-100 Sec
Oil Temp Trip Monitoring value of Oil temperature
above which Oil Temperature trip is
enabled.
This is only available if CAN Bus is
enabled.
100
40-250
Disabled*
Oil Temp Trip
Delay
Monitoring time for above.
5
1-100 Sec
Digital
Input 1 Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec
Digital
Input 2 Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec
Digital
Input 3 Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec