OilTemperature Oil Temperature.
Earth Fault
Earth fault.
Canopy
Temperature
Canopy Temperature fault.
ICON
DESCRIPTION NOTES
Start Failed
The engine has not fired after the programmed number of starts
attempts
Stop Failed
The controller has detected a condition that indicates that the
engine is running when it has been instructed to stop.
Engine High
Temperature
(HWT)
The controller detects that the engine coolant temperature has
exceeded the high engine temperature setting level and the Safety
On timer has expired.
Low Lube Oil
Pressure(LLOP)
The controller detects that the engine oil pressure has fallen below
the low oil pressure programmed level and the Safety On timer has
expired.
Under RPM
TheenginespeedhasfallenbelowtheprogrammedRPM
Over RPM
The engine speed has risen above the programmed RPM alarm
setting
V Belt/Chg Alt
The auxiliary charge alternator voltage is low
Low Fuel
The level detected by the fuel level sensor is below the low fuel level
setting.
Generator Under
Voltage
The generator output voltage has fallen below the programmed
setting after the Safety On timer has expired.
Generator Over
Voltage
The generator output voltage has risen above the programmed
setting and the Timer has expired.
Emergency Stop The emergency stop button has been depressed. This fail safe
(normally closed to emergency stop) input and will immediately stop
the set should the signal be removed.
LLOP Sensor
Open
Oil pressure sensor has been detected as being open circuit.
HWT Sensor
Open
HWT sensor has been detected as being open circuit.
FUEL Sensor
Open
Fuel sensor has been detected as being open circuit.
RWL
RWL fault.
Oil Level
Oil level fault.
R P M
R P M