Pick Up RPM
Source
The source of RPM which shall be used to
terminate the crank
Gen Vol
Gen Voltage
MPU CAN Bus(if
CAN Enabled)
Cnk Dsc LLOP
Sw
Auto disconnects the crank command on
detection of Oil pressure from switch.
Disabled
Enabled
Disabled*
Cnk Dsc LLOP
Sn
Auto disconnects the crank command on
detection of Oil pressure from sensor.
Disabled
Enabled
Disabled*
Cnk Dsc Alt
Vol
The minimum voltage from Charging
alternator which shall be deemed fit
enough to disconnect the crank.
5
Disabled*
3-40V
Service Due HrTime, in hours, for next service due. This
is warning/reminder.
250
10-999 Hrs
Pick Up KVA
warning
I
f the programmable Digital output is
programmed for “Load Warning” The digital
output shall be activated on crossing the load
KVA above the programmed level.
8
1-9999
Reset KVA
warning
Once the load falls below this level the
above activated contact shall be released.
8
1-9999
KVA
Warning Delay
The supervision time for the above 2
parameters.
5
1-999 Sec
Choke Pre
time
If the programmable Digital output is
programmed for “Heater /Choke”
This parameter sets the time gap between
this contact and crank. The crank will be
activated after the programmed time has
elapsed after this contact was activated.
Disabled
Disabled*
1-100 Sec
Choke Post
time
If the programmable Digital output is
programmed for “Heater /Choke”
Keep the choke for this time after the engine
has started.
Disabled
Disabled*
1-100 Sec
Pump/ Sol Pre
Time
Activate the Pump/Sol Pre Time by this time
before cranking when solenoid type is
selected as “pull to start”.
2
1-100Sec
KVA
KVA
KVA