tolerated before stopping the
Generator. This setting is not
available if (4)&(5) are disabled.
RPM
Source
RPM can be selected through MPU
or CAN Bus.
MPU
MPU
CAN Bus
Pick Up
RPM
This parameter specifies the
minimum RPM at which crank shall
be terminated.
900
200-3000
Cnk Dsc
LLOP Sw
Auto disconnects the crank
command on detection of Oil
pressure from switch.
Disabled
Enabled
Disabled*
Cnk Dsc
LLOP Sn
Auto disconnects the crank
command on detection of Oil
pressure from sensor.
Disabled
Enabled
Disabled*
Cnk Dsc Alt
Vol
The minimum voltage from
Charging alternator which shall be
deemed fit enough to disconnect
the crank.
5
Disabled*
3-40V
Service
Due Hr
Time, in hours, for next service
due. This is warning/reminder.
250
10-999 Hrs
Pick Up
KVA
warning
If the programmable Digital output
is programmed for “Load Warning”
The digital output shall be
activated on crossing the load KVA
above the programmed level.
8
1-9999
Reset KVA
warning
Once the load falls below this level
the above activated contact shall
be released.
8
1-9999
KVA
Warning
Delay
The supervision time for the above
2 parameters.
5
1-999 Sec