Action LLOP
Select the action when LLOP
fault occurs.
Engine Shut Down
Warning
Engine Shut Down
No Action
HWT Trip Level Monitoring value of water
temperature above which HET
trip is generated.
90
40-249
Disabled*
HWT Trip Delay Monitoring time for above.
5
1-100 Sec
Action HWT
Select the action when HWT
fault occurs.
Engine Shut Down
Warning
Engine Shut Down
No Action
Oil Temp Trip
Monitoring value of Oil
temperature above which Oil
Temperature trip is enabled.
100
40-250
Disabled*
Oil Temp Trip
Delay
Monitoring time for above.
5
1-100 Sec
Action Oil Temp Select the action when Oil
Temperature fault occurs.
Engine Shut Down
Warning
Engine Shut Down
No Action
Digital
Input 1 Delay
Monitoring time for
programmable digital input.
Digital inputs are explained
above.
5
1-100 Sec
Action DIN 1 Select the action when any
parameter of digital input 1 is
selected.
Engine Shut Down
Warning
Engine Shut Down
No Action
Digital
Input 2 Delay
Monitoring time for
programmable digital input.
Digital inputs are explained
above.
5
1-100 Sec
A
cti
on DIN 2Select
the action when
Engine Shut Down
Warning
Engine Shut Down
No Action