Choke Pre
time
If the programmable Digital output
is programmed for “Heater
/Choke”
This parameter sets the time gap
between this contact and crank.
The crank will be activated after
the programmed time has elapsed
after this contact was activated.
Disabled
Disabled*
1-100 Sec
Choke Post
time
If the programmable Digital output
is programmed for “Heater
/Choke”.
Keep the choke for this time after
the engine has started.
Disabled
Disabled*
1-100 Sec
Pump/ Sol
Pre Time
Activate the Pump/Sol Pre Time by
this time before cranking when
solenoid type is selected as “pull to
start”.
2
1-100Sec
13.3 Protection Parameter
Fuel Warn Level Monitoring value of fuel level
below which fuel level warning is
generated.
15
Disabled*
11-80 %
Fuel Warn Delay Monitoring time for above.
10
1-100 Sec
Fuel Trip Level Monitoring value of fuel level
below which fuel level trip is
generated.
15
10-80 %
Disabled*
Fuel Trip Delay Monitoring time for above.
10
1-100 Sec
LLOP Trip Level Monitoring value of lube oil
pressure below which LLOP trip
is generated.
1.0
0.4-8.5 Kg/cm
2
Disabled*
LLOP Trip Delay Monitoring time for above.
5
1-100 Sec