background image

 

20 

CARE AND MAINTENANCE 
 

 

WARNING: 

Failure to keep primary air openings of burners clean may result in sooting and property damage.  

 

  CAUTION:

 You must keep control areas, burner, and circulating air passageways of heater clean. Inspect these 

areas of heater before each use. Have heater inspected yearly by a qualified service person. Heater may need more 
frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.  

 

The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. 
Keep these holes clear of dust, dirt and lint. Clean these air inlet holes prior to each heating season. Blocked air holes 
will create soot. We recommend that you clean the unit every 500 hours of operation or every three months. 

 

MAIN BURNER 

Periodically inspect all burner flame holes with the heater running. All slotted burner flame holes should be open with 
yellow flame present. All round burner flame holes should be open with a small blue flame Present. Some burner flame 
holes may become blocked by debris or rust, with no flame present. If so, turn off heater and let cool, either remove 
blockage or replace burner. Blocked burner flame holes will create soot. 

 

CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE 

We recommend that you clean the unit every three months or after 2500 hours of operation. We also recommend that you 

keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using 

compressed air no greater than 30 PSI. You can use a vacuum cleaner in the blow position. If using compressed air in a 

can, please follow the directions on the can. If you don't follow directions on the can, you could damage the pilot assembly. 

 

1. 

Shut off the unit, including the pilot. Allow the  

unit to cool for at least thirty minutes.  

2. 

Inspect burner, pilot and primary air inlet holes  

on injector holder for dust and dirt (see Figure 26).  

3. 

Blow  air through the ports/slots and holes in  

the burner. 

4. 

Check the injector holder located at the  

end of the burner tube again.  Remove any large 
particles of dust, dirt, lint, or pet hair with a soft cloth or 
vacuum cleaner nozzle. 

5. 

Blow air into the primary air holes on the 

injector holder. 

6. 

In case any large clumps of dust have now 

been pushed into the burner.  Repeat steps  
3 and 4. Clean the pilot assembly also.  

 

CLEANING ODS/PILOT 

Use a vacuum cleaner, pressurized air, or a small,  
soft bristled brush to clean. 

 

A yellow tip on the pilot flame indicates dust and dirt in  
the pilot assembly.  There is as mall pilot air inlet hole  
about two inches from where the pilot flame comes out of the  
pilot assembly (see Figure 27).  With the unit off, lightly blow air through the air inlet hole.   
You may blow through a drinking straw if compressed air is not available 

 

CABINET 
Air Passageways 

      

 Use a vacuum cleaner or pressurized air to clean. 

Exterior 

      

 Use a soft cloth dampened with a mild soap and water mixture. 

      

 Wipe the cabinet to remove dust. 

 

LOGS 

      

 If you remove logs for cleaning, refer to Installing Logs to properly replace logs. 

      

 Replace log(s) if broken or chipped (dime-size or larger). 

 

BLOWER (OPTIONAL ACCESSORY) 

Refer to model QEB100 manual.

 

Figure 26 Inject or holder on 
outlet burner tube

 

Figure 27

 

Summary of Contents for BD23TCC-2-LO

Page 1: ...TY This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion an...

Page 2: ...x 23 000 BTU Hr 23 000 BTU Hr 23 000 BTU Hr 23 000 BTU Hr Input Min 14 000 BTU Hr 19 000 BTU Hr 14 000 BTU Hr 19 000 BTU Hr Gas Type Natural LP Propane Natural LP Propane Ignition Electronic Piezo Ele...

Page 3: ...s that alter burner flame patterns which can cause sooting WARNING Do not use a blower insert heat exchange insert or other accessory not approved for use with this heater Due to high temperatures the...

Page 4: ...Do not add extra logs or ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base Rock and debris could fall into the control ar...

Page 5: ...ust be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy o...

Page 6: ...approximately one 1 ounce 30ml of water for every 1 000 BTUs 3kWs of gas input per hour An unvented room heater is recommended as a supplemental heater a room rather than a primary heat source an enti...

Page 7: ...of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors are...

Page 8: ...mum the space can support BTU hr actual amount of BTU hr used Example 51 200 BTU hr maximum the space can support 56 000 BTU hr actual amount of BTU hr used The space in the above example is a confine...

Page 9: ...permanent openings one within 12 inches of the ceiling and one within 12 inches of the floor Connect these items directly to the outdoors or spaces open to the outdoors see figure 3 These spaces incl...

Page 10: ...etc in the air exist may cause walls to discolor WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoining side and back walls IMPORTANT Vent free...

Page 11: ...ed equipment shutoff valve with 1 8 in NPT tap is an acceptable alternative to test gauge connection Purchase the optional CSA design certified equipment shutoff valve from your dealer WARNING Never c...

Page 12: ...Hold gas regulator with wrench when connecting into gas piping and or fittings NG Models 5 in to 10 5 in W C Gas supplier provide external regulator for natural gas Purchase the optional CSA design c...

Page 13: ...the width of a quarter and turn knob counterclockwise until the knob locks into the LP position see Figure 10 Selection valve must be locked into either the LP position or the NG position 3 Rotate and...

Page 14: ...system Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected...

Page 15: ...structions in this manual Flames contacting logs will create soot Figure 13 Installing Log Set IMPORTANT Make sure log does not cover any burner ports see Figure13 It is very important to install the...

Page 16: ...s heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call...

Page 17: ...ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for repairs Until repairs are made light pilot with match 7 Keep control knob press...

Page 18: ...rward 2 Follow steps 1 through 5 under Lighting Instructions 3 With Control Knob in PILOT position strike match and hold near pilot Press in Control Knob pilot should light 4 Keep Control Knob pressed...

Page 19: ...ting page 21 23 BURNER FLAME PATTERN Figure 24 shows a correct burner flame pattern Figure 25 shows an incorrect burner flame pattern If pilot flame pattern is incorrect then Turn heater off see To Tu...

Page 20: ...no greater than 30 PSI You can use a vacuum cleaner in the blow position If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could d...

Page 21: ...wrong 2 Ignitor electrode is broken 3 Ignitor electrode is not connected to ignitor cable 4 Ignitor cable is pinched or wet 5 Damaged ignitor cable 6 Bad piezo ignitor 7 Low battery 1 Replace electrod...

Page 22: ...tomer service 3 Contact your gas supplier Delayed ignition of burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner see Care and maintenance Pa...

Page 23: ...furniture 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into white powder residue 1 Turn heater off when using furniture polish wax carpet cleaner or similar products He...

Page 24: ...r Service or your dealer have ready Your name Your address Model and serial number of your heater How heater was malfunctioning Type of gas used Propane LP or Natural gas NG Purchase date Usually we w...

Page 25: ...1 FBB28D01 B Burner Assembly 1 2 NDD0308 400 DF ODS 1 3 SIT545 200 T Stat Valve Assembly 1 4 AL092 01 PIMSC1 01 Piezo Ignitor 1 5 RV83FI 4 9 DF Regulator 1 6 YDF06 BD23T Gas Selection Valve Assembly 1...

Page 26: ...ront Panel Left 1 1 6 BD230T104 Lower Front Panel Right 1 1 7 BD230T109 Door 1 1 8 BD230T005 Decorative Trim Assembly 1 1 9 BD230T003 Firebox Assembly 1 1 10 BD230T004 Louver Assembly 1 1 11 BD230T201...

Page 27: ...27 Printed in China...

Reviews: