51
Duration of power
supply failure
Action before power
supply failure
Action after power supply failure
< 2 minutes
In
“Ignition
”
mode
The controller will continue
working as normal
In
“Burning
”
mode
The controller verifies the
air/water temperature
and continues the burning phase
or restarts in
“Ignition
”
phase
˃ 2 minutes
In
“Ignition
”
mode
The controller continues its
normal operation
In
“Burning
”
mode
If the flue gas temperature
dropped below 55°С
the device will restart.
If their temperature is at least
55°С, the operation continues in
“
Burning
”
mode.
5.3.15.
Work phases and sequence of processes
Work phase
Work sequence
Functions
OFF
(SWITCHED
OFF)
Switched off
Testing the good working order of the system
and monitoring the anti
-
freezing temperature.
Maintaining the fire
Automatic starting up and maintaining ambient
temperature of 4 to 8°С
.
FIREU
P
(IGNITION)
Testing for fire
Verification of the anti
-
freezing combustion
process.
Warming up
Warming up
the igniter.
Ignition
of fuel
Sucking in hot air through the fuel.
Testing the
ignition
Checking for available fire and cutting off the
voltage to the igniter.
Summary of Contents for KPW 24
Page 3: ...3 5 3 14 21 5 3 15 22 5 4 23 6 26 6 1 26 6 2 27 6 3 27 7 29 8 29 9 31...
Page 4: ...4 1 1 1 1 1 1 1 4 1 1...
Page 5: ...5 1 2...
Page 6: ...6 1 3 2 1 1 2 230V50Hz 3 WiFi 4 40mm 5 1 6 4...
Page 9: ...9 10 3 1 EN14785 2006 EN 55014 EN 60335 EN 61000 EC 2015 1185 3 2 4...
Page 10: ...10 2 4 1 100 cm 40cm 50cm 40cm 20cm 4 2...
Page 11: ...11 3m 5 4 3...
Page 12: ...12 4 4 1 1 2 230V50Hz 3 WiFi 4 40mm 5 1 6 4 5 230V 50Hz...
Page 13: ...13 4 6 6mm 30mm 4 8 4 9 N plus 1 EN ISO 17225 2 2014 5 5 1...
Page 14: ...14 30 5 2 250W 1 5 30 Start Stop...
Page 15: ...15 5 3 Fumis Premium 3 1 3 6 3 Start Stop 3...
Page 16: ...16 Fumis Premium USB 5 3 1 23 5 18 0 5 3 2 5 3 3...
Page 17: ...17 5 3 4 NO I03 GND WiFi 5 3 5 A1 6 35 40 1 5 3 6...
Page 19: ...19 5 3 8 3 20 C 4 C 5 3 9 30 30...
Page 20: ...20 5 3 10 OFF LOW HI LOW OFF LOW HI 5 3 11 50 80 2 51...
Page 22: ...22 2 2 55 55 5 3 15 OFF 4 8 FIREUP...
Page 24: ...24 A002 A003 A004 A005 E001 E101 E102 1 2 3 4 E105...
Page 25: ...25 E106 E108 E109 E110 E111 E113 E114 E115 1 1 2 https prity bg com...
Page 26: ...26 6 6 1 4 4 5 5...
Page 27: ...27 6 2 1 2 6 3 5 6...
Page 28: ...28 2 4 6 7 https prity bg com...
Page 29: ...29 7 http prity bg com service 359 878 881 354 8 36 3600 1500...
Page 30: ...30 01 02 2022...
Page 31: ...31 9 112 115 112 115 95 33 www prity bg com...
Page 61: ......
Page 62: ......
Page 63: ......