SIMULATE
The level simulation function can be used to verify that the pumps are starting and stopping according
to the level set points. This function allows the operator to manually raise or lower the measured level.
Caution:
Pump will start and stop while using this function. Pump dry run is possible if no backup floats
are used or by-passed.
Note: the level simulation screen will time out after 10 seconds of inactivity and return to the measure
level.
PRIMEX
®
10 Station View
™
Controller User Manual