I/O STATUS (ADVANCED SETUP)
These screens can be used to view all the digital and analog inputs and relay output status. It is a
good trouble-shooting feature. Digital inputs and output change color when ON.
INPUT TERMINALS
DUPLEX TRANSDUCER BASED
DUPLEX FLOAT BASED
TERM
INPUT
TYPE
DESCRIPTION
DESCRIPTION
15
I0 DIGITAL PNP
ILLEGAL ENTRY (OPTIONAL)
ILLEGAL ENTRY (OPTIONAL)
PUMP 1 IN AUTO MODE
14
I1 DIGITAL PNP
PUMP 1 IN AUTO MODE
13
I2 DIGITAL PNP
PUMP 2 IN AUTO MODE
PUMP 2 IN AUTO MODE
12
I3 DIGITAL PNP
PUMP 1 RUNNING
PUMP 1 RUNNING
11
I4 DIGITAL PNP
PUMP 2 RUNNING
PUMP 2 RUNNING
10
I5 DIGITAL PNP
POWER FAIL
POWER FAIL
9
I6 DIGITAL PNP
LOW FLOAT (BACKUP - MONITOR ONLY)
STOP ALL PUMP FLOAT
8
I7 DIGITAL PNP
START LEAD PUMP FLOAT
7
I8 DIGITAL PNP
START LAG PUMP FLOAT
6
I9 DIGITAL PNP
HIGH FLOAT (BACKUP - MONITOR ONLY)
HIGH LEVEL FLOAT
5
AN1 4-20 mA
LEVEL TRANSDUCER
NOT USED
4
AN0 4-20 mA
MOTOR AMPS
MOTOR AMPS
3
GRND
GROUND
GROUND
2
0V
POWER SUPPLY 0V
POWER SUPPLY 0V
1
24V
POWER 24Vdc
POWER 24Vdc
OUTPUT TERMINALS
DUPLEX TRANSDUCER BASED
DUPLEX FLOAT BASED
TERM
INPUT
TYPE
DESCRIPTION
DESCRIPTION
1
O0
RELAY C
RUN PUMP 1 IN AUTO
RUN PUMP 1 IN AUTO
2
RELAY NO
3
O1
RELAY C
RUN PUMP 2 IN AUTO
RUN PUMP 2 IN AUTO
4
RELAY NO
5
O2
RELAY C
GENERAL ALARM
GENERAL ALARM
6
RELAY NO
7
O3
RELAY C
GENERAL ALARM (USER)
GENERAL ALARM (USER)
8
RELAY NO
9
O4
RELAY C
PUMP 1 FAULT (USER)
PUMP 1 FAULT (USER)
10
RELAY NO
11
O5
RELAY C
PUMP 2 FAULT (USER)
PUMP 2 FAULT (USER)
12
RELAY NO
13
O6
TRANSISTOR
HIGH LEVEL XDCR (USER)
NOT USED
14
O7
TRANSISTOR
LOW LEVEL FLOAT (XDCR MODE) - (USER)
NOT USED