background image

SET LEVELS

This screen is only accessible if in “Level Transducer” mode. This mode is used for setting the level 

set point for proper pump operation.

Use            for decimal point. Max input value is 99.9 ft.

Stop

 = Stop level. All pumps will stop when the level drops below this value.

Start

 = Start level. The lead pump will start when the level rises above this value.

Lag

 = Lag level. The lag pump will start when the level rises above this value.

High

 = High level alarm. Activates the beacon and horn.

When the lead or lag pump starts, they will continue to run (latched) until the level drops below the stop 

level or a fault occurs. Only pumps in AUTO will run.

Backup float switch operation:

A backup control method independent of the Station View controller is strongly recommended. 
A typical 2 backup float system would operate the following way:
High level float:

All pumps will run when activated until the level drops below the Low level float. Activates the alarm 

beacon and horn.
Low level float:
If the level drops  below the Low level float switch, it will stop any pump operation in automatic mode. 

The purpose of the Low level float switch is to protect the pumps against damage  resulting from dry 

run condition.

Note:  There are 2 digital inputs on the StationView for High Level and Low Level floats.  These inputs 

are only for monitoring and do not control the pumps.

An external controller is the only way to the control the pumps in the event of a Station View controller 

failure

PRIMEX

®

                                                                            9                                         Station View

 Controller User Manual

Summary of Contents for STATION VIEW

Page 1: ...STATION VIEWTM DUPLEX PUMP CONTROLLER User Manual 1 844 4PRIMEX 477 4639 WWW PRIMEXCONTROLS COM...

Page 2: ...Alarms 5 Alarm History 6 Alternation 7 Datalog 8 Set Levels 9 Simulate 10 Advanced Setup Navigation 11 System Sensor 12 Flow 13 Flow continued Amps 14 Dry Run High Amp 15 Date Time Max Run Time Passw...

Page 3: ...accumulating within the controller housing ELECTRICAL SHOCK HAZARD A qualified service person must install and service this product according to applicable codes and electrical schematics Disconnect...

Page 4: ...toring Pump level in feet bar graph Float switch status indication when using float switches Pump GPM using volumetric calculation with level transducer PUMP CONTROL AND PROTECTION Automatic pump alte...

Page 5: ...PROGRAMMING MAIN SCREEN The main screen gives the operator an overview of the lift station status Level Transducer Mode Float Switches Mode PRIMEX 2 Station View Controller User Manual...

Page 6: ...KEY PAD OPERATION The controller keypad is used for screen navigation and data entry PRIMEX 3 Station View Controller User Manual...

Page 7: ...MAIN MENU NAVIGATION Navigation from the Main screen to the Menu Screens Press to go back to the previous screen at any time PRIMEX 4 Station View Controller User Manual...

Page 8: ...sducer check low level float check pump 6 LEVEL SENSOR OPEN Transducer signal is less than 4mA Check transducer connection check trans ducer and vent tube 7 LEVEL SENSOR SHORT Transducer signal is mor...

Page 9: ...ccessed via the Alarm Menu The last 14 alarm events are recorded with time and date stamp The last alarm recorded is displayed first Use the to view previous alarms Press to go back to the previous sc...

Page 10: ...on sequence to start the same pump every time This is typically done to equalize run times If 1 2 is selected P1 will start every time and P2 will only be used as a lag pump If 2 1 is selected P2 will...

Page 11: ...data is very useful for tracking high in flow events and pump performance Cyc number of cycles pump starts min pump run time in minutes gal gallons pumped only available if a level transducer is used...

Page 12: ...itch operation A backup control method independent of the Station View controller is strongly recommended A typical 2 backup float system would operate the following way High level float All pumps wil...

Page 13: ...allows the operator to manually raise or lower the measured level Caution Pump will start and stop while using this function Pump dry run is possible if no backup floats are used or by passed Note th...

Page 14: ...ADVANCED SETUP MENU NAVIGATION Press to go back to the previous screen at any time PRIMEX 11 Station View Controller User Manual...

Page 15: ...Set 20mA 23 0 ft Some transducers are already calibrated in ft Max value for 20mA is 99 9 ft When using a submersible pressure transducer 0 0 ft represents the level at the bottom of the transducer a...

Page 16: ...Calc level set points and the fill and discharge times Both In Flow and Discharge flow are calculated during every cycle PRIMEX 13 Station View Controller User Manual Tank Diameter Enter the tank dia...

Page 17: ...User Manual The Station View controller uses a single current sensor input for multiple pumps It combines the pump run input with the current signal to determine the current for each pump The measurin...

Page 18: ...ps on Dry Run the next pump will be called to run The Dry Run fault automatically reset after 2 minutes Set to 0 0A to disable this function HIGH AMP ADVANCED SETUP High Amp Alarm also uses the motor...

Page 19: ...to prevent unauthorized access to the Menu Set to 0 to disable this function PUMP DATA ADVANCED SETUP The Pump Data screen is for information only It is a record of the pump HP Volts and FLA This dat...

Page 20: ...LEAD PUMP FLOAT 7 I8 DIGITAL PNP START LAG PUMP FLOAT 6 I9 DIGITAL PNP HIGH FLOAT BACKUP MONITOR ONLY HIGH LEVEL FLOAT 5 AN1 4 20 mA LEVEL TRANSDUCER NOT USED 4 AN0 4 20 mA MOTOR AMPS MOTOR AMPS 3 GRN...

Page 21: ...I O TERMINAL CONFIGURATION DIMENSIONS AND MOUNTING PRIMEX 18 Station View Controller User Manual...

Page 22: ...PN 1038494D 10 20 2018 SJE Inc All Rights Reserved PRIMEX is a trademark of SJE Inc 1 844 4PRIMEX 477 4639 WWW PRIMEXCONTROLS COM...

Reviews: