Connect Bell Controller to Dry Contact Switch
The Bell Controller dry contact closure inputs can be connected to a standalone switch or button to activate a bell manually - commonly
referred to as an impromptu bell. An impromptu bell is a bell event that is not scheduled in OneVue.
How to connect bell controller device to dry contact switch or button
Be sure to follow the installation requirements and installation location guidelines.
The removable terminal connector is provided for simple wiring. The wiring procedure is as follows:
1.
All power to the device and equipment wiring the device to must be turned off.
2.
Remove the terminal connector from the device and make the wiring connections to the terminals.
P1: Input 1 for impromptu bell (switch or button input) – dry contact closure input pair sounds bell(s) on both relays immediately
when activated
P2: Input 2 for impromptu bell (switch or button input)
Terminals accept wire gauge from 16-26 AWG.
3.
Reconnect terminal connector to device.
4.
Apply power to device.
WARNING:
Make sure the wires are properly attached to the terminals and the terminal connections are tight. Wires are to be stripped
and there are no loose strands that can cause a short.
18
PrimexEVENT Series - Bell Controller Installation Guide