
27
System Setup & Faults
POWERING DOWN
Cause:
Occurs when the 120VAC that powers the
PressCam 8 is removed. Current data is
saved and system locks up to prevent data
from being corrupted.
Cure:
1) Check power input to Presscam 8.
Especially if you are using 24VDC. Your
supply may not be able to handle the
load.
2)
Consult
factory.
QUALITY CHECK LIMIT REACHED
Cause:
The Part Count
fi
eld reached the Quality
Count setpoint causing the Counter Output
to drop out.
Cure:
Push the Knob to reset in either RUN or
PROG modes. Part Count
fi
eld will reset
to 0.
RELAY OFF S/B ON
Cause:
Output #15 or #16 relay detected off but
should be energized (on)
Cure:
1) Excessive electrical noise.
2)
Bad
relay.
3)
Faulty
circuitry.
RELAY ON S/B OFF
Cause:
Output #15 or #16 relay detected energized,
but should be off.
Cure:
1) Relay contact welded closed.
2) Excessive electrical noise.
3)
Bad
relay.
4)
Faulty
circuitry.
RESOLVER FAULT 1,2,3,or 4
Cause
: Hardware problem (1), jumping backwards
(2), jumping forwards (3), wrong voltage
levels (4)
Cure
: (same as before)
Check
: Unplug the 8pos connector from the PCB.
Expect about 21 ohms RED to BLK wires,
44 ohms GRN to BLK or WHT to BLK
wires.
SLAVE FAILURE
Cause:
The slave computer is not sending valid data
back to the master.
Cure:
1) Excessive electrical noise.
2)
Computer
failure.
SLV DATA or JOB FLT
Cause
: Data transfer between computers failed
Cure
: 1) Check for Electrical Noise
2) Check Job memory chip
3) Check Hardware
SPM > 999
Cause:
Unit is only designed to operate up to 999
SPM. If you are not operating outside this
range, then there is a fault in the system.
Cure:
1) The resolver is faulty.
2) Excessive electrical noise.
3)
Computer
failure.
TDC OFFSET FLT 1 or 2 (Top Dead Center)
Cause
: Master (1) or Slave (2) reports the OFF
SET does not match the other
Cure
: 1) Off-Line job programmer setup
incorrectly.
2) Faulty Job memory chip(s)
3) Electrical Noise
4) Faulty circuitry
TONNAGE BELOW MINIMUM
Cause:
Tonnage never rose above minimum during
the stroke.
Cure:
1) Connection from Load Module to
Presscam 8 is bad.
2) Minimum set too high.
3) Computer board bad.
4) Load module bad or needs calibration.
TONNAGE ABOVE MAXIMUM
Cause:
Tonnage above maximum during the stroke.
Cure:
1) Adjust your stamping pressure.
2) Maximum set too low for job.
3) Computer board bad.
4) Load module bad or needs calibration.
TONNAGE A/D FAULT
Cause:
Calibration input used by the computer is
not reading correctly
Cure:
1) Computer board bad.
Summary of Contents for PressCam 8
Page 1: ...PressCam 8 Installation Operations Manual ...
Page 2: ...Rev 5 0 ...
Page 14: ...6 Internal Wiring Diagram 28 101 System Installation ...
Page 15: ...7 Control Box Dimensions 28 102 System Installation ...
Page 16: ...8 Panel Cut Out Dimensions 28 103 System Installation ...
Page 17: ...9 Control Panel Dimensions 28 104 System Installation ...
Page 18: ...10 System Installation External Wiring Diagram 28 105 ...
Page 19: ...11 System Installation I O Board Dimensions 28 106 ...
Page 44: ...36 Tonnage Load Monitor optional Installation T400 Installation ...