Precision HWST Installation And Operating Instructions Manual Download Page 6

 

3.1.2

   Install the safety relief valve(s) on the pipes provided.  Plumb the relief valve outlet connections full size to the floor 

drain.  Check local codes for proper safety valve discharge for steam boilers above 15 psi, which normally are required to 
be piped to overhead discharge outside safely away from personnel. 

      

3.1.3

 Hot water boilers may be equipped with an air vent pipe on the top of the boiler.  Plumb this connection to the   

      expansion tank or install an automatic air vent on this pipe

    

3.1.4

   The direction of flow through hot water boilers and water heaters must be from the inlet to the outlet (IE: bottom   

      to top).  Do not reverse these connections. 

 

      NOTE:  Do not oversize feedwater piping and values on steam boilers, as this may result in severe pressure fluctuations   
      during feedwater cycles if the fill rate is too rapid. 
 

 

     3.2   Electrical Connections 

       3.2.1   Power Feed Wiring 

      The recommended wire size is listed on both the unit’s Bill of Material (BOM) and the Wiring Diagram (WD).  Also, the full  
      load amperage and maximum voltage are stamped on the unit’s nameplate.  The feeder must be sized for 125% of the  
      full load amperage in accordance with Article 424-3 of the NEC.  The wiring must have insulation rated  
      75°C or greater. Copper wiring is recommended for all power connections.  The recommended size is noted in the ‘Notes”  
      on the wiring diagram. 
 

      CAUTION:  Do not exceed the maximum voltage as listed on the nameplate.  For resistance loads, amperage increases 
      proportionally with voltage. 
 
 

3.2.2 Equipment Grounding Conductors 

 

The unit is equipped with grounding lugs(s) inside the power panel(s). The grounding conductors must be installed and 

 

sized in accordance with NEC Article 424-14. The recommended size is noted in the “Notes” on the diagram.  

3.2.3   Control Wiring 

Alteration of, or additions to, control wiring may void both the Underwriters Laboratories Listing and the Manufacturer’s  
Limited Warranty.  Field-installed controls, control connections, and modifications must be approved in writing by the  
Factory. 
 

NOTE:

  All power connections are 3-Phase, 3-Wire.  (Exception:  If unit is single phase.)  There is no provision for a neutral  

connection; (IE: the unit should not be wired ‘wye’ or ‘star’

). 

 

 

    3.3  Filling the System 

3.3.1

   The system and the boiler / water heater must be thoroughly flushed before the final fill.  Steam boilers should be 

“boiled out” before operation. 

3.3.2   Water Treatment

 

Consult a local water treatment firm for recommendations on proper water treatment and boilout procedure to prevent 
damage to the boiler vessel, components and heating elements.  The internal materials of boilers are Steel, Incoloy and 
Cast Iron, which all are compatible with standard boilout compounds.  In lieu of a commercial boilout compound, the 
following mix of chemicals can be used for every 1,000 gallons of water: 

 

30 lbs. TSP (tri-sodium phosphate; Na

3

PO

4

), commonly found in many building supply centers

 

5 lbs. caustic soda (50% pure sodium hydroxide; NaOH) 

 

2 lbs. ordinary powdered laundry detergent. (Example: Tide) 

      

These chemicals should be dissolved in warm water prior to their addition to the boiler.  The boiler should be heated for at 
least 3 hours, then drained and flushed

 

 

NOTE:

  Standard hot water boilers are suitable for ethylene glycol mixtures up to a 50/50 mix

 
   

 

Summary of Contents for HWST

Page 1: ...Installation and Operating Instructions ELECTRIC HOT WATER STEAM BOILERS...

Page 2: ...injury or property damage Read this manual thoroughly and follow the instructions herein The PRECISION Boilers shall be installed according to the procedures detailed in this manual or the Precision...

Page 3: ...2 Operating Instructions 9 5 2 2 Electric Door Interlocks 9 5 2 4 120 Volt Power Source 9 5 2 6 Alarm and Reset Circuits 9 5 2 7 Sequencing of Element Circuits 9 6 0 SEQUENCE OF OPERATION 6 1 Activati...

Page 4: ...f the authorities having jurisdiction 1 3 Recommendations 1 3 1 Preventative Maintenance A Preventative Maintenance Schedule is provided as a recommendation for periodic equipment Inspections Recordin...

Page 5: ...rs are not suitable for placement on combustible flooring 2 4 2 Leave a permanent space for element removal opposite element access panels as shown on the Dimensional Drawing DD and 36 inches opposite...

Page 6: ...ors The unit is equipped with grounding lugs s inside the power panel s The grounding conductors must be installed and sized in accordance with NEC Article 424 14 The recommended size is noted in the...

Page 7: ...fuses Then check the resistance phase to phase for all three phases Make sure that there are no short circuits phase to phase or phase to ground With a megger 500VDC minimum check contactor load side...

Page 8: ...t during the first day of operation the affected element will not be energized allowing the hot water to drive the moisture out at a controlled rate 4 4 3 Removal of Moisture in Element method 2 An al...

Page 9: ...same margin as specified for high limits to be above the controller setting 5 2 Operating Instructions 5 2 1 With the unit s control power ON OFF or ON OFF PREHEAT switch OFF close the main power swi...

Page 10: ...tactor coil circuits 6 2 2 Proportional Step Controls 6 2 2 1 Step Control Sequence The controller senses the unit s water temperature either via 135 ohm device or thermistor or steam pressure either...

Page 11: ...int the step controller should bring on nominally one half of the steps An adjustable proportional band is provided on the controller sensor to enable tuning the unit to system demand 7 1 2 Solid Stat...

Page 12: ...cause an automatic inverse change of 1 F at the control point NOTE Refer to the applicable vendor literature provided on both the setpoint controls and step controls installed in your boiler 8 0 PREV...

Page 13: ...k torque on element flange bolts The acceptable torque range is 10 15 ft lbs CAUTION Do not over tighten elements 8 4 2 Remove and replace any leaking elements or element gaskets Inspect handhole and...

Page 14: ...ement gaskets should be replaced immediately upon leak detection 8 5 1 Adequately tag wire and then remove wires from defective elements 8 5 2 Remove element by removing the four 4 attachment nuts 8 5...

Reviews: