Precision HWST Installation And Operating Instructions Manual Download Page 13

13 

 

8.3   Electrical System Maintenance 

8.3.1

   Clean the control cabinets periodically (as often as needed) to keep both the interior and the exterior 

free of dust, moisture and foreign matter.  The interior cleaning of the electrical panels must be done with the 

POWER OFF! 
 
NOTE:

  For units supplied with control cabinet cooling fans, the condition of the fan

 

filter must be periodically 

checked and the filters cleaned or replaced as necessary. 
 

8.3.2

   With the POWER OFF, periodically check the tightness of electrical connections; particularly at power 

entrance lugs, fuses (line side) and contractors (load side).  This should be done at time of commissioning, at 7 – 
14 days thereafter and at least annually.  Replace any components that show signs of heat damage (IE:  
discoloration, charring, melted insulation, etc

.). 

8.3.3

   Inspect the condition of the contactors.  Look for burned or corroded contacts or overheated coils and 

wires.  If the contactors chatter or hum during operation, they should be either disassembled and cleaned to 
remove dust or other foreign material in the mechanism or replaced. 

8.3.4

   Inspect the heating elements.  Make sure that the terminal contacts are tight, clean, and corrosion-free. 

8.3.5

   Check all the wiring throughout the unit for frayed or brittle insulation.  Replace any wiring showing 

insulation degradation. 
 

8.4   Boiler Mechanical System Maintenance 

8.4.1

   With the POWER OFF, remove the element access covers.  Inspect all internal vessel connections, 

particularly at the heating elements.  Spot check torque on element flange bolts.  The acceptable torque range is 
10 – 15 ft. lbs

 

CAUTION:  Do not over tighten elements

 

8.4.2

   Remove and replace any leaking elements or element gaskets.  Inspect

 

handhole and manhole gaskets.  If 

these gaskets are brittle, they should

 

replaced. 

       
 

WARNING:

  Over-torquing of the elements nuts will damage the element gasket. 

 
 

8.4.3

   Repair any leak at any place on the unit or adjacent piping.  Re-torque flange bolts on system piping. 

8.4.4   

For all boilers, the interior of the pressure vessel must be inspected at least once a year.  If there is any 

presence of scale, refer to ‘Preventative Maintenance Water Treatment’ above a consult a local water 
treatment firm immediately.  Scale formation on the elements will cause heating element failures.  Scale 
formation elsewhere in the boiler can cause erratic control operation / failure, particularly on water level 
controls

8.4.5

   When the boiler is inspected, rod out the pipes to the water column(s) and inspect the operation of the 

float(s) in the level controller(s

). 

8.4.6

   Remove and clean the low water cutoff probe. 

8.4.7

   Steam Boiler Special Maintenance 

8.4.7.1

   All PRECISION steam boilers are supplied with a surface blow-off connection.  If surface blowoff valves 

are not Factory-installed, they should be installed in the field.  The surface blow-off should be used as often as 
necessary to remove organics which accumulate at the water surface, and to limit TDS.  (Boiler

 

water TDS 

should not exceed 3500 ppm

). 

8.4.7.2

   Both the boiler and water column should be blown down periodically to remove bottom sludge

8.4.7.3

   The water column should be blown down daily to assure proper operation of the level control / LWCO 

assembly

8.4.7.4

   

Water Treatment

 

Summary of Contents for HWST

Page 1: ...Installation and Operating Instructions ELECTRIC HOT WATER STEAM BOILERS...

Page 2: ...injury or property damage Read this manual thoroughly and follow the instructions herein The PRECISION Boilers shall be installed according to the procedures detailed in this manual or the Precision...

Page 3: ...2 Operating Instructions 9 5 2 2 Electric Door Interlocks 9 5 2 4 120 Volt Power Source 9 5 2 6 Alarm and Reset Circuits 9 5 2 7 Sequencing of Element Circuits 9 6 0 SEQUENCE OF OPERATION 6 1 Activati...

Page 4: ...f the authorities having jurisdiction 1 3 Recommendations 1 3 1 Preventative Maintenance A Preventative Maintenance Schedule is provided as a recommendation for periodic equipment Inspections Recordin...

Page 5: ...rs are not suitable for placement on combustible flooring 2 4 2 Leave a permanent space for element removal opposite element access panels as shown on the Dimensional Drawing DD and 36 inches opposite...

Page 6: ...ors The unit is equipped with grounding lugs s inside the power panel s The grounding conductors must be installed and sized in accordance with NEC Article 424 14 The recommended size is noted in the...

Page 7: ...fuses Then check the resistance phase to phase for all three phases Make sure that there are no short circuits phase to phase or phase to ground With a megger 500VDC minimum check contactor load side...

Page 8: ...t during the first day of operation the affected element will not be energized allowing the hot water to drive the moisture out at a controlled rate 4 4 3 Removal of Moisture in Element method 2 An al...

Page 9: ...same margin as specified for high limits to be above the controller setting 5 2 Operating Instructions 5 2 1 With the unit s control power ON OFF or ON OFF PREHEAT switch OFF close the main power swi...

Page 10: ...tactor coil circuits 6 2 2 Proportional Step Controls 6 2 2 1 Step Control Sequence The controller senses the unit s water temperature either via 135 ohm device or thermistor or steam pressure either...

Page 11: ...int the step controller should bring on nominally one half of the steps An adjustable proportional band is provided on the controller sensor to enable tuning the unit to system demand 7 1 2 Solid Stat...

Page 12: ...cause an automatic inverse change of 1 F at the control point NOTE Refer to the applicable vendor literature provided on both the setpoint controls and step controls installed in your boiler 8 0 PREV...

Page 13: ...k torque on element flange bolts The acceptable torque range is 10 15 ft lbs CAUTION Do not over tighten elements 8 4 2 Remove and replace any leaking elements or element gaskets Inspect handhole and...

Page 14: ...ement gaskets should be replaced immediately upon leak detection 8 5 1 Adequately tag wire and then remove wires from defective elements 8 5 2 Remove element by removing the four 4 attachment nuts 8 5...

Reviews: