Precision HWST Installation And Operating Instructions Manual Download Page 11

11 

 

6.2.3  Recycle Feature 

All step controls now incorporate the recycle feature which returns the step control to the no-load condition 
upon loss of control power

 

6.2.4   Manual Step ‘ENABLE / DISABLE’ Toggle Switches 

All units with >1 step now include manual ‘ENABLE / DISABLE’ toggle switches to provide a positive ‘OFF’ 
override of each step.  These are used to disable a faulty step, limit total output or allow for a slow preheat. 
 

6.2.5   Preheat Switch (Boilers Only) 

The preheat switch is a manual limit switch.  In order to preheat the boiler, the ON/OFF/PREHEAT switch must 
be in the

 

down position.  When the ON/OFF/PREHEAT switch is in its down or PREHEAT position, the boiler 

output is limited to approximately 25% of full load power.  This allows the operator to limit the boiler output 
during startup cycles (particularly if the boiler is shut off at night and turned on again in the morning), which 
could lessen electrical demand charges. 
When the boiler has been brought up to the setpoint temperature (or pressure), the ON/OFF/PREHEAT switch is 
moved slowly from its down or PREHEAT position to its up or ON position passing through the OFF position to 
cause the step control to recycle to the NO LOAD position.  Thereafter, the boiler can operate up to full load if 
necessary. 
 

NOTE

:  The PREHEAT switch is included as an option on boilers of 9 or more steps.  It is intended to be used to 

prevent setting demand peaks on ‘cold starts’.  It does not have to be used if so desired. 
 
 
 

7.0   OPERATIONAL TESTING 

 

7.1   Standard Controls

 

7.1.1   135-ohm Controllers (T991,T915,L91,etc.) 

With the water temperature (or steam pressure) at setpoint, the step controller should bring on nominally one 
half of the steps.  An adjustable proportional band is provided on the controller (sensor) to enable tuning the 
unit to system demand. 

7.1.2   Solid State Controls 

With the water temperature (or pressure) at setpoint, the step controller should bring on nominally one half of 
the steps.  An adjustable proportional band is provided on the controller (sensor) to enable tuning the unit to 
system demand. 
IMPORTANT:  The timing between stages adjustable (with step control).  Steam boilers normally have delay of 
between 15-20 seconds while stepping up and 3-5 seconds while stepping down.  Water boilers can normally 
respond slower so 25 – 40 seconds up and 5 – 10 seconds down is usually appropriate.  The slower the step 
sequencing, the less wear on both the contractors and heating elements (yet still able to control the process as 
needed) the less heat is generated in the cabinet which results in longer component life. 
 

7.2   Outdoor Reset Controls 

7.2.1   135-ohm Type Outdoor Reset Controller (Hot Water Boilers Only) (Honeywell T991B type) 

These controllers have a fixed reset ratio:  either 1-to-1, 1-to-1.5 or 1.5-to-1.  The outdoor reference 
temperature is 70°F (IE:  the boiler outlet water control point temperature is equal to the setting on the 
controller when the outdoor temperature, at the outdoor bulb, is 70°F).  In order to test the operation of this 
controller. 

7.2.1.1   

Check the outdoor temperature at the outdoor air sensing bulb; then determine the number of degrees 

this temperature is above, or below 70°F.

 

7.2.1.2   

Check the boiler outlet water temperature; if the outdoor temperature is below 70°, multiply the 

difference between 70°F and the actual outdoor temperature by the reset ratio (1.0, .67 or 1.5); and subtract 
this from the temperature of the boiler outlet water

Summary of Contents for HWST

Page 1: ...Installation and Operating Instructions ELECTRIC HOT WATER STEAM BOILERS...

Page 2: ...injury or property damage Read this manual thoroughly and follow the instructions herein The PRECISION Boilers shall be installed according to the procedures detailed in this manual or the Precision...

Page 3: ...2 Operating Instructions 9 5 2 2 Electric Door Interlocks 9 5 2 4 120 Volt Power Source 9 5 2 6 Alarm and Reset Circuits 9 5 2 7 Sequencing of Element Circuits 9 6 0 SEQUENCE OF OPERATION 6 1 Activati...

Page 4: ...f the authorities having jurisdiction 1 3 Recommendations 1 3 1 Preventative Maintenance A Preventative Maintenance Schedule is provided as a recommendation for periodic equipment Inspections Recordin...

Page 5: ...rs are not suitable for placement on combustible flooring 2 4 2 Leave a permanent space for element removal opposite element access panels as shown on the Dimensional Drawing DD and 36 inches opposite...

Page 6: ...ors The unit is equipped with grounding lugs s inside the power panel s The grounding conductors must be installed and sized in accordance with NEC Article 424 14 The recommended size is noted in the...

Page 7: ...fuses Then check the resistance phase to phase for all three phases Make sure that there are no short circuits phase to phase or phase to ground With a megger 500VDC minimum check contactor load side...

Page 8: ...t during the first day of operation the affected element will not be energized allowing the hot water to drive the moisture out at a controlled rate 4 4 3 Removal of Moisture in Element method 2 An al...

Page 9: ...same margin as specified for high limits to be above the controller setting 5 2 Operating Instructions 5 2 1 With the unit s control power ON OFF or ON OFF PREHEAT switch OFF close the main power swi...

Page 10: ...tactor coil circuits 6 2 2 Proportional Step Controls 6 2 2 1 Step Control Sequence The controller senses the unit s water temperature either via 135 ohm device or thermistor or steam pressure either...

Page 11: ...int the step controller should bring on nominally one half of the steps An adjustable proportional band is provided on the controller sensor to enable tuning the unit to system demand 7 1 2 Solid Stat...

Page 12: ...cause an automatic inverse change of 1 F at the control point NOTE Refer to the applicable vendor literature provided on both the setpoint controls and step controls installed in your boiler 8 0 PREV...

Page 13: ...k torque on element flange bolts The acceptable torque range is 10 15 ft lbs CAUTION Do not over tighten elements 8 4 2 Remove and replace any leaking elements or element gaskets Inspect handhole and...

Page 14: ...ement gaskets should be replaced immediately upon leak detection 8 5 1 Adequately tag wire and then remove wires from defective elements 8 5 2 Remove element by removing the four 4 attachment nuts 8 5...

Reviews: