ProtEX-MAX PD8-7000 Explosion-Proof Temperature Meter Instruction Manual
20
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure
across F4 and COM, or with an active low signal applied to F4.
Figure 16. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA output are made to the connector terminals labeled MA OUT. The 4-20 mA
output may be powered internally or from an external power supply.
Figure 17. 4-20 mA Output Connections
Power Supply for Analog Output Loop or Other Uses
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the
analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as
interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This
feature is enabled by configuring the relay, and relative digital input(s) (see page 37). In one example, dry
interlock contacts are connected in series to one digital input which will be used to force on (energize) the
assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front
panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O
contact). See below.
Figure 18. Interlock Connections
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
R
I-
I+
1
3
2
RELAY1
3
2
1
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
R
I-
I+
MA OUT
1
3
2
RELAY1
3
2
1
24 V
MA OUT