ProtEX-MAX PD8-7000 Explosion-Proof Temperature Meter Instruction Manual
25
Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation. The
following table shows the main menu functions and messages in the order they appear in the menu.
Display
Parameter Action/Setting
Description
setup
Setup
Enter
Setup
menu
Input
Input
Enter
Input
selection
menu
tc
TC
Set meter for
thermocouple input
J, K, T, E, R, S, B, N,
C
Rtd
RTD
Set meter for RTD
input
100Pt, 1000Pt, 10Cu,
120Ni
A385
A385
Set meter for 0.00385
curve
A392
A392
Set meter for 0.00392
curve
F or C
F or C
Press Enter to select
degrees F or C
unitS
Units
Select the display
units/tags
Dec pt
Decimal
point
Set decimal point
dddd, dddd.d,
dddd
°
F, dddd.dF
dsplay
Display
Enter the
Display
menu
Line 1
Line 1
Press Enter to assign
the upper display
parameter (default:
PV - temperature)
Line 2
Line 2
Press Enter to assign
the lower display
parameter (default:
engineering units)
d-Inty
Display
intensity
Set display intensity
level from 1 to 8
RELaY
Relay
Enter the
Relay
menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for
automatic reset
A-nman
Auto-
manual
Set relay for
automatic & manual
reset
any time
LatcH
Latching
Set relay for latching
operation
Display
Parameter Action/Setting
Description
Lt-CLr
Latching-
cleared
Set relay for latching
operation with manual
reset only after alarm
condition has cleared
Altern
Alternate
Set relay for
alternation control
Sanmpl
Sampling
Set relay for sampling
operation
OFF
Off
Disable relay and
front panel status
LED (Select Off to
enable Interlock
feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-4 setup
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe
operation
on
On
Enable fail-safe
operation
off
Off
Disable fail-safe
operation
FLS 2
Fail-safe 2
Set relays 2-4 fail-
safe operation
DeLAY
Delay
Enter relay
Time
Delay
menu
DLY 1
Delay 1
Enter relay 1 time
delay setup
On 1
On 1
Set relay 1 On time
delay
OFF 1
Off 1
Set relay 1 Off time
delay
DLY 2
Delay 2
Enter relays 2-4 time
delay setup
break
Break
Set relay condition if
input break detected
ignore
Ignore
Ignore input break
condition
(Processed as an
upscale condition)
On
On
Relay goes to alarm
condition when input
break is detected