ProtEX PD8-6080/PD8-6081 Explosion-Proof Modbus
®
Scanner Instruction Manual
80
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the scanner.
Parameter
Display
Default Setting
Mode
mode
Master
Function Code
FunCod
03
PV Number
Pv.nbr
PV1-PV4
Enabled
Slave ID PV1-16
Slav.Id
001 - 016
Register
Number PV1-16
Reg.nbr
40001
Data Type PV1-
16
Data
Float
Byte Order
1234
Big-endian
Polling Time
t-poll
5.0 second
Slave Response
Timeout
t-resp
10.0 second
Serial
Serial
Scanner ID
SCAn.Id
246
Baud
baud
9600
Parity
parity
Even
Byte-to-byte
timeout
t-byte
0.01 second
Setup
Setup
Tag
PV1-16
Tag
Pv1
PV 1
– PV 16
Units
PV1-16
Units
Pv1
FEET
Units C1-4
Units
Ch C1
UnitC1
– UnitC4
Display
Format PV1-16
Formt
Pv1
Dec (PD6080)
Ft-In-16 (PD6081)
Display
Format C1-4
Formt
Ch C1
Decimal
Display decimal
point
Disp.dp
ddd.ddd
Float decimal
point
Flot.dp
ddd.ddd
Number of
points
No pts
2 (all PVs and C
channels)
Scaling
SCalE
pv 1
All
Input 1
InP 1
0.000
Display 1
Dis 1
0.000
Input 2
InP 2
10.000
Display 2
Dis 2
10.000
Math, channel
C1-4
Sum
Sum
Parameter
Display
Default Setting
Adder (constant
P)
Adder
0.000
Factor (constant
F)
Factor
1.000
Filter
Filter
Filter, PV 1
Ch-A
70
Filter, PV 2
Ch-B
70
Bypass, PV 1
bypass
0.2
Bypass, PV 2
bypass
0.2
Round
Round
1
Cutoff
Cutoff
Cutoff value, PV
1
Ch-a
0.000 (disabled)
Cutoff value, PV
2
Ch-b
0.000 (disabled)
Display
assignment
Dsplay
Line 1
D pv
Display PV
Line 2
d tag
Display tag
Display intensity
d-Inty
8
Relay 1
assignment
Pv 1
PV 1
Relay 1 action
Act 1
Automatic
Relay 1 set point
Set 1
1.000
Relay 1 reset
point
RSt 1
0.500
Relay 2
assignment
Pv 2
PV 2
Relay 2 action
Act 2
Automatic
Relay 2 set point
Set 2
2.000
Relay 2 reset
point
RSt 2
1.500
Relay 3
assignment
Pv 3
PV 3
Relay 3 action
Act 3
Automatic
Relay 3 set point
Set 3
3.000
Relay 3 reset
point
RSt 3
2.500
Relay 4
assignment
Pv 4
PV 4
Relay 4 action
Act 4
Automatic
Relay 4 set point
Set 4
4.000