PD6800 Loop-Powered Process Meter Instruction Manual
7
OVERALL
DIMENSIONS
5.65" x 5.25" x 4.86" (W x H x D)
(144 mm x 133 mm x 124 mm)
WEIGHT
5.00 lbs (80 oz, 2.27 kg)
WARRANTY
3 years parts and labor
Input
ACCURACY
±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span.
ADVANCED
FUNCTION
Linear, square root, or programmable exponent
MULTI-POINT
LINEARIZATION
2 to 32 points
PROGRAMMABLE
EXPONENT
1.0001 to 2.9999
LOW FLOW CUTOFF
0-99999 (0 disables cutoff function)
TEMPERATURE
DRIFT
50 PPM/
C from -40 to 75
C ambient
DECIMAL POINT
User selectable decimal point
MINIMUM SPAN
Input 1 & Input 2: 0.10 mA
CALIBRATION
RANGE
An
Error
message will appear if input 1 and input 2 signals
are too close together.
Input
Range
Minimum Span
Input 1 & Input 2
4-20 mA
0.10 mA
MAXIMUM
VOLTAGE DROP
Without Backlight or with
Externally-Powered (DC
Powered) Backlight
With Loop-Powered
Backlight
3.0 VDC @ 20 mA
6.0 VDC @ 20 mA
EQUIVALENT
RESISTANCE
150
Ω
@ 20 mA
300
Ω
@ 20 mA
EXTERNALLY
POWERED
BACKLIGHT
Voltage Range:
Maximum Power
9-36 VDC
9 VDC 12 VDC 24 VDC 36 VDC
0.2 W 0.25 W 0.5 W
0.75 W
INPUT
OVERLOAD
Over current protection to 2 A max.