PD6800 Loop-Powered Process Meter Instruction Manual
30
For instructions on how to program numeric values
see
Setting Numeric Values
, page 20.
Indication (
INDICAT
)
The
Indication
menu is used to enable and set up a high or low alarm indication on
the screen. When alarm indication is enabled, the HI and LO symbols are used
accompanied by a flashing display.
INDICAT
ALRNm
INDICAT
off
INDICAT
set
ALARM
Enter
Set Point
1
6.000
SET
reset
ALARM
Enter
Reset Point
1
6.000
RESET
Accept
Setting
Accept
Setting
Alarm (
alrnm
)
High alarm trip point:
program set point above reset point.
Low alarm trip point:
program set point below reset point.
Alarm deadband is determined by the difference between set and reset
points. Minimum deadband is one display count. If set and reset points are
programmed the same, output will reset one count below set point.
To acknowledge a rate or total alarm, press the
Enter
button once for
acknowledge prompt and a second time to confirm.