Model PD655 Large Display Process Meter
Instruction Manual
40
Round Horizontal Tank Calibration Points
Number of Points: 10
Maximum Error: 0.3% F.S.
Input mA
Display
(%
Volume)
1 4.00
0.00
2 4.80
1.80
3
6.00
7.20
4 7.20
14.20
5 9.20
28.10
6 14.80
71.80
7 16.80
85.80
8 18.00
92.80
9 19.20
98.10
10 20.00
100.00
Number of Points: 8
Maximum Error: 0.5% F.S.
Input mA
Display
(%
Volume)
1 4.00
0.00
2 4.80
1.90
3 6.40
9.50
4 8.40
22.40
5 15.60
77.70
6 17.60
90.50
7 19.20
98.10
8 20.00
100.00
Calibration Error (
error
)
A meter display of
Error
during calibration indicates that the calibration process
was not successful. The meter should be recalibrated.
The
Error
message will appear if input 1 signal and input 2 signal are too close
together. Refer to
Minimum Input Span (Error Message)
, page 35.
The
Error
message will appear if input 1 signal is inadvertently also applied for
input 2 calibration, or
ENTER
is pressed before applying input 2.