Model PD655 Large Display Process Meter
Instruction Manual
22
OP
T
ION
S
PCB
Figure 4.
Options Board Connectors and J5 Jumper
Wiring Instructions
Refer to Figure 3 and Figure 4 for connectors’ location.
1. All field connections to be made with insulated copper wire, either solid or
stranded. Tighten all screw terminals to 4.5 lb-in (0.5 Nm).
Strip length = ¼ in (7 mm).
DO NOT
pre-treat wire with solder.
2.
Terminals Earth Ground, L2(V-), L1(V+) on J2 (Main Board) and
terminals 1-6 on J3-J4 (Options Board):
Use AWG #12-18 wire, 600 volt,
60
°
C. Connect only one wire to each terminal.
3.
Terminals EN, AK, R, CM, S+, S-, P-, P+, P1-, P1+ on J1 (Main Board)
and ter, - (Options Board):
Use AWG #12-22 wire, 150 volt, 60
°
C.
If using AWG #20 or smaller wire, up to two wires may be connected to each
terminal. If using AWG #18 or larger wire, only one wire may be connected
to each terminal.
4. Install conduit hubs to the enclosure cable input ports. To maintain NEMA
4X rating use only UL/CSA watertight conduit hubs.
5. Feed all wires through the enclosure cable input ports.
6. Remove one connector at a time from the headers and connect the wires to
the connector.
7. After wiring a connector, insert it back into the header.
Terminals Designation
Terminal Description
Terminal
Description
L1, L2
AC input power
CM
Common (return) for
R, AK, EN
V+, V-
DC input power
R
External total reset
Earth ground
AK
External relay
acknowledge
P+, P-
24 VDC transmitter
power supply
EN
External
enter
P1+, P1-
24 VDC output
power supply
+, -
4-20 mA output
S+, S-
Input signal
1-6 Relay
1-4