Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
39
Multi-Point Linearization Utility
The meter can be programmed for multi-point scaling using the PC-
based Multi-Point Linearization Utility available for free download at
www.predig.com.
In order to program the meter using a computer, the meter must be con-
nected using an RS-232 or RS-485 serial adapter, see ORDERING IN-
FORMATION on page 7 for details.
Scaling the Meter (
SCALE
)
The process inputs (4-20 mA and
±
10 VDC) can be scaled to display the
process variable in engineering units.
A signal source is not needed to scale the meter; simply program the
inputs and corresponding display values.
SCALE
Prog
Inp 1
SCALE
0
4.000
I n p 1
Inp 2
SCALE
2
0.000
I n p 2
dis 1
SCALE
0
04.000
d i s 1
dis 2
SCALE
0
20.000
d i s 2
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 33.