Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
10
LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
,
or
dddddd
CALIBRATION
RANGE
Input
Range
Minimum Span
Input 1 & Input 2
4-20 mA 0.15 mA
±
10 V
0.10 V
An Error message will appear if the input 1 and input 2
signals are too close together.
INPUT
IMPEDANCE
Voltage ranges: greater than 1 M
Ω
Current ranges: 50 - 100
Ω
(depending on resettable fuse impedance)
INPUT
OVERLOAD
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
Rate/Totalizer
DISPLAY
ASSIGNMENT
The main (Big) and small (Little) displays may be assigned
to rate, total, grand total, alternate R & T, units, and set
point.
RATE DISPLAY
INDICATION
-99999 to 999999, lead zero blanking. “R” LED illuminates
while displaying rate.
TOTAL DISPLAY
& TOTAL
OVERFLOW
0 to 999,999; automatic lead zero blanking. “T” LED is illumi-
nated while displaying total or grand total.
Up to 999,999,999 with total-overflow feature. “
oF
” is dis-
played to the left of total overflow and
▲
LED is illuminated.
ALTERNATING
DISPLAY
Either display may be programmed to alternate between
rate and total or rate and grand total every 10 seconds.
TOTAL
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
,
or
dddddd
Total decimal point is independent of rate decimal point.
TOTALIZER
Calculates total based on rate and field programmable mul-
tiplier to display total in engineering units. Time base must
be selected according to the time units in which the rate is
displayed.
TOTALIZER
ROLLOVER
Totalizer rolls over when display exceeds 999,999,999.
Relay status reflects display.
TOTALIZER
PRESETS
Up to eight, user selectable under setup menu. Any set
point can be assigned to total and may be programmed
anywhere in the range of the meter for total alarm indica-
tion.