Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
29
Display Parameter
Action/Setting
Description
Asign1
Assign 1
Relay 1 assignment
rATE
Rate
Assign relay to rate
totAL
Total
Assign relay to total
G total
Grand total
Assign relay to grand total
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-man
Auto-manual
Set relay for automatic & manual reset
any time
LatCH
Latching
Set relay for latching operation (relays
assigned to rate)
Lt-CLr
Latching-
cleared
Set relay for latching operation with ma-
nual reset only after alarm condition has
cleared (relays assigned to rate)
Altern
Alternate
Set relay for pump alternation control
(relays assigned to rate)
Sampl
Sampling
Set relay for sampling operation
OFF
Off
Disable relay and front panel status LED
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown, only if ex-
pansion relay module is installed.
FaiLSF
Fail-safe
Enter
Fail-safe
menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation
on
On
Enable fail-safe operation
off
Fail-safe off
Disable fail-safe operation
DeLAY
Delay
Enter relay
Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On
Set relay 1 On time delay
OFF 1
Off
Set relay 1 Off time delay
break
Loop break
Set relay condition if loop break detected
(For mA input only)