Model PD6200 Analog Input Rate/Totalizer
Instruction Manual
35
Setting the Input Signal (
input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or vol-
tage (
volt
) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
±
10 VDC signals.
Setting the Totalizer Features (
total
)
Enable or disable the totalizer features by selecting “
Yes
” or “
no
” after
the input type has been set up. If the totalizer features are disabled, all
the totalizer features and functions are hidden from the menus.
Note: The totalizer continues working in the background.
Setting the Decimal Point (
dEc pt
)
The decimal point may be set with up to five decimal places or with no
decimal point at all. The rate, total, and grand total decimal points are
independent.
Pressing the Right arrow moves the decimal point one place to the right
until no decimal point is displayed then it moves to the leftmost position.
Setting the Display Parameter & Intensity (
dsplay
)
The main display (
Big
) can be programmed to display:
1. Rate
value
2. Total or grand total
3. Relay
set
points
4. Max & min values
The small display (
Little
) can be programmed to display:
1. Rate
value
2. Total or grand total
3. Relay
set
points
4. Max & min values
5. Engineering units or custom legends
6. Off (no display)
Display Intensity: The meter has eight display intensity levels to give the
best performance under various lighting conditions. Select intensity 8 for
outdoor applications.