Helios Large Display Dual Analog Input Rate/Totalizer Instruction Manual
PD2-6262
34
Total and Grand Total Setup
The time base
and total
conversion
factor, and grand
total conversion
factor for input channels A
and B are located in the
Totalizer Setup
menu.
The time base is based on the
rate of flow. Total & grand total
conversion factors for channel
A and B are programmed
independently. The total and
grand total have their own
independent settings. This
means that one can be
displaying the value in gallons
while the other displays in million gallons, liters, m
3
, etc.
Total & Grand Total Reset
Total reset menus are located in the
Program
menu. The totals can be programmed for
manual or automatic reset. In the automatic
reset mode, a programmable time delay is
available to reset the total or grand total after the
assigned preset is reached.
Password Protected and Non-Resettable Total
The total and grand total can be password-protected to prevent unauthorized resets. The grand total can
be programmed as a non-resettable total, see page 47 for details.