PD2-6262 Helios Large Display Analog Dual-Input Rate/Totalizer Instruction Manual
29
Setting the Input Signal (
Input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or voltage (
volt
) inputs for channel A
and channel B.
The current input is capable of accepting any signal from 0 to 20 mA. Select current input to accept 0-20
mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC. Select voltage input to accept 0-
5, 1-5, 0-10, or
10 VDC signals.
Channel C is the Math Function calculation, which is set up in the Advanced Features menu.
Setting the Totalizer Features (
total
)
Enable or disable the totalizer features by selecting “
Yes
” or “
no
” after the input type has been set up for
each channel. If the totalizer features are disabled, all the totalizer features and functions are hidden from
the menus. Level and process meter features and functions are added to the menus.
To simply not display the total, select alternative display parameters in the display (
dsplay
) menu.
If disabling the
total
parameter by selecting
no
, please refer to the PD2-6060 manual available at
www.predig.com for instructions on setting up the meter parameters.
Notes: 1. The totalizer continues working in the background.
2. When selecting "no" for Total for a channel, the meter now functions as a PD2-6060 Dual-Input
Process Meter
for parameters that affect that channel
. We strongly suggest that you download
and use the PD2-6060 instruction manual from our website (www.predig.com) while in this mode of
operation.