Loop Leader PD6620 Series Loop-Powered Rate/Totalizer Instruction Manual
21
Parameter
Action/Setting Description
START
Start a batch
STOP
Stop a batch
STR-STP
Start or stop a batch
PRESET
Preset batch amount
ALARM.FN
Set the function key or digital input
to acknowledge an alarm or ac-
cess set points
ACK
Acknowledge all active alarms
SETPOINT
Access all output set points
SETPT.OC1
Access open collector 1 set point
SETPT.OC2
Access open collector 2 set point
SETPT.R1
Access relay 1 set point
SETPT.R2
Access relay 2 set point
SWATCH.FN
Set the function key or digital input
to activate stopwatch
START
Start the stopwatch
STOP
Pause/Stop the stopwatch
STR-STP
Start or stop the stopwatch
HOLD FN
Set the function key or digital input
to hold an output
HOLD.OUT
Hold all outputs
HLD.UNHLD
Hold or un-hold all outputs
OC1+2
Hold/un-hold open collector out-
puts
RLY1+2
Hold/un-hold relay outputs
mAOUT
Hold/un-hold 4-20 mA output
HOLD
Hold selected output
HLD.UNHLD
Hold or un-hold selected output
DISABLE
Disable the function key or digital
input
RST FN
Set the function key or digital input
to reset a value
RESET
Reset min, max, or max/min PV
value
R MIN.MAX
Reset max and min PV value
RST T
Reset the total
RST GT
Reset the grand total
RST T.GT
Reset the total and grand total
HINT
Display hint text on first key press
and execute action on second key
press
OFF
Turn the hint function off
ON
Turn the hint function on
SYSTEM
Program system settings
AOUTCAL
Calibrate the analog output
DEFAULT
Reset meter to factory defaults
TOTAL
Enable or disable the totalizer
ENABLE
Enable the totalizer (Default)
DISABLE
Disable the totalizer (see PD6602
manual)
BACKLITE
Enable or disable the display back-
light
Parameter
Action/Setting Description
ENABLE
Enable the backlight (default)
DISABLE
Disable the backlight
INFO
View meter software, version, and
model, and change the meter iden-
tifier tag
SFT
The software ID number
VER
The software version
MODEL
The meter hardware model num-
ber
ID.TAG
The meter identifier tag
Press
Enter
to edit tag
ICAL
Internal calibration used for scaling
DISPLAY
Program the meter’s display
UNITS
Change the display units within the
selected unit class
DEC.PT
Change the decimal point location
RATE
Program the rate decimal point
TOTAL
Program the total decimal point
GTOTAL
Program the grand total decimal
point
COMMA
Enable or disable the use of a
comma to separate the thousands
place on the bottom display
ENABLE
Enable comma (default)
DISABLE
Disable comma
TOP
Set what to display on the top line
RATE
Display the rate
RATE+U
Display the rate and its units alter-
nating
TOTAL
Display the total
TOTAL+U
Display the total and its units alter-
nating
GTOTAL
Display the grand total
TAG
Display the tag
UNITS
Display the units
PRESET
Display the preset value
STPWATCH
Display the stopwatch
TIMR OC1
Display open collector 1 timer
TIMR OC2
Display open collector 2 timer
TIMER R1
Display relay 1 timer
TIMER R2
Display relay 2 timer
MIN
Display minimum value
MAX
Display maximum value
MIN MAX
Display alternating min and max
BOTTOM
Set what to display on the bottom
line
TOTAL
Display the total
TOTAL+U
Display the total and its units alter-
nating
TOT+TAG
Display the total and its tag alter-
nating
T+U+RU
Display the total, its units, and the
rate units alternating