Loop Leader PD6620 Series Loop-Powered Rate/Totalizer Instruction Manual
33
Solid State Relay Outputs (
RELAY
)
The meter is optionally equipped with two solid state relays that may be set up for alarms, sample, timer,
or batch control. Alternatively, they may be disabled.
Alarms are available based on the rate, total, or grand total value, or the digital input. The alarm status
will show on the display even if the output is not wired.
Sample will engage the relay for a programmed period of time when either the total or the grand total
have reach a programmed amount.
A timer output (
TIMER
) turns the relay on and off at the specified time intervals. The timer can be set as
single-shot or continuous timer.
For use in batch control applications, the meter relays may be set to batch. This will enable the batch
control features of the meter.
The stopwatch output (
STPWATCH
) allows the relay to be manually activated by starting the stopwatch.
The stopwatch count can be displayed on the top or bottom line.
The output may be disabled by selecting
DISABLE
.
Caution!
During setup, the relays do not follow the
input and they will remain in the state
found prior to entering the Relay menu.
!
SETUP
OUTPUT
OPEN
COLLECTR
OUT
RELAY
RELAY
OUTPUT1
RELAY
OUTPUT2
RELAY
INFO
INFO
RELAY 1
INFO
RELAY 2
RLY 1
DISABLE
RLY 1
ALARM
RLY 1
SAMPLE
RLY 1
TIMER
ALARM
RATE
ALARM
D.INPUT
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
SAMPL
TOTAL
SAMPL
GTOTAL
RLY 1
BATCH
BATCH
COUNT
BATCH
MAXIMUM
BATCH
MODE
BATCH
PRESET
BATCH
DELAY
ALARM
TOTAL
ALARM
GTOTAL
RLY 1
STPWATCH