Troubleshooting / Quick Reference Guide
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
37
EMERGENCY
STOP
RED
Unit will not start in AUTO
with mains power loss.
Check screen for
additional information.
Verify emergency stop button is
disengaged (pulled out). Clear alarm.
LOW BATTERY
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Clear alarm. Using control panel, inspect
battery by navigating to BATTERY MENU
option from MAIN MENU. If battery
condition displays GOOD, contact an
IASD. If control panel displays CHECK
BATTERY, replace battery.
BATTERY
PROBLEM
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Contact an IASD.
CHARGER
WARNING
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Contact an IASD.
SERVICE A
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Perform SERVICE A maintenance. Press
ENTER to clear.
SERVICE B
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Perform SERVICE B maintenance. Press
ENTER to clear.
INSPECT
BATTERY
YELLOW
Yellow LED illuminated in
any state.
Check screen for
additional information.
Inspect battery. Press ENTER to clear.
Active Alarm
LED
Problem
Things to Check