Maintenance
26
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
Intake Side Panel Removal
See
. The intake side panel (B) must be
removed to access battery compartment, fuel regulator,
and sediment trap. Proceed as follows to remove the
intake side panel:
Figure 4-2. Remove Intake Side Panel
1.
Raise lid and remove front panel.
2.
Use a 4 mm hex key to remove two mounting
screws (A) and L-bracket screw (C).
3.
Lift intake panel up and away from generator set.
NOTE:
Always lift intake side panel straight up before
pulling away from enclosure. Do not pull panel away from
enclosure before lifting up (D).
Performing Scheduled Maintenance
It is important to perform maintenance as specified in the
for correct generator set operation.
Engine oil and oil filter must be changed, and valve clear-
ance adjusted after first 25 hours of operation.
Emissions-critical maintenance must be performed as
scheduled in order for emissions warranty to be valid.
Emissions-critical maintenance consists of servicing the
air filter and spark plugs in accordance with the
The controller will prompt for Schedule A or Schedule B
maintenance to be performed. Schedule A maintenance
consists of the oil, oil filter, and battery check. Schedule B
maintenance includes the oil, oil filter, battery check, air
cleaner, spark plug(s), and valve clearance.
Since most maintenance alerts will occur at the same
time (most have two year intervals), only one will appear
on the control panel display at a time. Once first alert is
cleared, next active alert will be displayed.