EC DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 5331
Name: 2-Wire programmable transmitter
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1 : 2006
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
The ATEX Directive 94/9/EC and later amendments
EN 50014 : 1997 + A1, A2, EN 50020 : 2002 and
EN 50284 : 1999
IEC 61241-0 : 2004 and IEC 61241-11 : 2005
ATEX certificate: KEMA 06ATEX0062 X (5331D)
No changes are required to enable compliance with the replacement standards:
EN 60079-0 : 2006 and EN 60079-11 : 2007
Notified body
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, 24 February 2009
Peter Rasmussen
Manufacturer’s
signature
15
Safety instructions
Ex installation:
For a safe installation of 5331D in hazardous area the following must be
observed. The module must only be installed by qualified personnel who are
familiar with the national and international laws, directives and standards that
apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The sensor circuit is not infallibly galvanically isolated from the input
circuit. However, the galvanic isolation between the circuits is capable of
withstanding a test voltage of 500 Vac during 1 minute.
The transmitter must be mounted in an enclosure in order to provide a degree
of ingress protection of at least IP20.
In explosive atmospheres caused by air / dust mixtures:
The transmitter may only be installed in a potentially explosive atmosphere
caused by the presence of combustible dust when mounted in a metal
enclosure form B according to DIN 43729 that is providing a degree of
ingress protection of at least IP 6X in accordance with EN 60529, that is
suitable for the application and is correctly installed.
Cable entries and blanking elements shall be used that are suitable for the
application and correctly installed.
For an ambient temperature
≥
60°C, heat resistant cables shall be used with a
rating of at least 20 K above the ambient temperature.
Special conditions for safe use:
If the enclosure in which the transmitter is mounted is made of aluminium and
installed in Zone 0, 1 or Zone 20, 21 or 22 it shall not contain by weight more
than 6% in total of magnesium and titanium.
The additional enclosure of the apparatus shall be designed and/or installed in
such a way that, even in the event of rare incidents, ignition sources due to
impact and friction sparks are excluded.
14