DC Linear Current / Voltage Output
The DC Linear (0/4-20 mA) Current or (0-5/10V) Voltage output is also available at Terminal 6 (+)
and Terminal 4 (-) if the Output-1 is configured for DC Linear.
Figure 12.3 (c)
6
5
4
OUTPUT- 2
(Terminals : 7, 8, 9)
OUTPUT- 3
(Terminals : 16, 17, 18)
The Output-2 and Output-3 are available through plug-in modules. The modules are factory configured for either Relay / SSR
or DC Linear Voltage or DC Linear Current. The connection descriptions are the same as those described for Output-1.
POWER SUPPLY
(Terminals : 12, 13)
Figure 12.4
As standard, the controller is supplied with power connections suited for 85 to 264 VAC line supply. Use well-insulated copper
2
conductor wire of the size not smaller than 0.5mm for power supply connections. Connect Line (Phase) supply line to terminal
12 and the Neutral (Return) supply line to terminal 13 as shown in Figure 15.4. The controller is not provided with fuse and
power switch. If necessary, mount them separately. Use a time lag fuse rated 1A @ 240 VAC.
For DC Supply, connect Signal (+) & Common (-) to controller terminals 12 & 13, respectively.
Line
Neutral
12 (L)
13 (N)
2 Pole
Isolating Switch
Fuse
Power Supply
Terminal
User Manual
neuro 102
The indicator is designed for installation in an enclosure which provides
adequate protection against electric shock. Local regulations regarding
electrical installation should be rigidly observed. Consideration should
be given to prevention of access to the Power Supply terminals by
unauthorized personnel.
Caution