Settings
(Default Value)
Parameter Description
SOAK TIME-3
0 to 9999
(Default : 0)
RAMP RATE-4
0.00 to 99.99
(Default : 0.00)
TARGET SETPOINT-4
SOAK TIME-4
0 to 9999
(Default : 0)
(Default : -200)
Min. to Max. Range
Specified for the
selected Input Type
This parameter allows the user to set the strategy as regards what
the controller shall do after completion of a running Profile Cycle. If
this parameter is set to ‘Yes’, the controller keeps the Control
Output (s) OFF until a next ‘Profile Start Command’ is issued or the
Profile Cycle is aborted.;
If however, this parameter is set to ‘No’, the controller behaves as
a single loop controller and maintains the PV at the user set value
for the SP (control/Auxiliary).
OUTPUT OFF
(Default : No)
No
Yes
This parameter is expressed in the same unit and resolution as
that for PV. By default, this parameters value is set to the Minimum
Range value specified for the selected ‘Input Type’. If the ‘Input
Type’ is altered, this parameter value automatically set to the
Minimum Range value of the altered ‘Input Type’.
This parameter sets the time duration for which the Setpoint is
maintained at Target setpoint - 3. This segment is skipped if set to
0, that is, the Setpoint start ramping to Target Setpoint - 4 as soon
as it reaches to target Setpoint - 3.
This parameter is expressed in minutes and settable in 1 minute
resolution.
This parameter sets the rate at which the Setpoint ramps from
Target Setpoint - 3 to Target Sepoint - 4. The setting resolution of
this parameter is independent of the displayed PV resolution. If set
to 0, the Ramp Setpoint immediately equals to the Target Setpoint
- 4.
This parameter
sets the target level for the fourth ramp segment.
The Setpoint ramps to this level with Ramp Rate-4 from target
Setpoint - 3.
This parameter is expressed in the same unit and resolution as
that for PV. By default, this parameters value is set to the Minimum
Range value specified for the selected ‘Input Type’. If the ‘Input
Type’ is altered, this parameter value automatically set to the
Minimum Range value of the altered ‘Input Type’.
This parameter sets the time duration for which the Setpoint is
maintained at Target setpoint - 4. This segment is skipped if set to
0. The Profile Cycle is over at the end of this segment. If the
parameter ‘Output Off’ is set to ‘No’, the controller start controlling
the PV with respect to the SP (Control/Auxilary). If alarm type is
selected as ‘end of Profile’, the OP3 Relay/SSR (if fitted)
energizes for approximately 10 seconds at the end of this
segment.
This parameter is expressed in minutes and settable in 1 minute
resolution.