Chapter 5 Function parameter
168
No. Code Parameter name
Setting range
Factory
setting
Change
limit
504.
E3.07
AI1 terminal as a
function selection
of DI
0 to 50
0
★
505.
E3.08
AI2 terminal as a
function selection
of DI
0 to 50
0
★
506.
E3.09 Reserved
507.
E3.10
Effective mode
selection when AI
as DI
Units digit
:
AI1
0:High level effectively
1:Low level effectively
Tens digit:AI2(0 to 1,same as units
digit)
Hundreds digit: Reserved
000
★
This group function code is used when using AI as DI, when AI used as DI, and input
voltage of AI is greater than 7V, AI terminal status will be high level, when input voltage of
AI is lower than 3V, AI terminal status will be low level. For between 3V~ 7V hysteresis
E3.10 is to determine that when the AI is used as DI, AI is made valid by means of the high
level state, or the low level of valid states. As for AI as DI feature set, same as the ordinary
DI Settings, please refer to the F1 group setting instructions related DI.
Below figure is AI input voltage taken as an example, explains the relationship between
input voltage of AI and the corresponding state of DI:
508.
E3.11
Virtual VDO1
output function
selection
With the physical internal
sub DIx
0
0
☆
See F2 group physical DO
output option
1to40
AI
Input
voltage
Judgment of effective state of AI
time
t
DC7V
DC3V
ON
ON
OFF
AI
Termina
l
status