Chapter 5 Function parameter
107
F1.20
Minimum input value
for AI curve 3
0.00V to F1.22
0.00V
☆
F1.21
Minimum input
setting for AI curve 3
-100.00% to 100.0%
0.0%
☆
F1.22
Maximum input for AI
curve 3
F1.20 to 10.00V
10.00V
☆
F1.23
Maximum input
setting for AI curve 3
-100.0% to 100.0%
100.0%
☆
For the function and use of curve 3, please refer to the description of curve 1.
F1.24
AI curve selection
Units
digit
AI1 curve selection
0x321
☆
Curve 1 (2 points, see
F1.12 to F1.15)
1
Curve 2 (2 points, see
F1.16 to F1.19)
2
Curve 3 (2 points, see
F1.20 to F1.23)
3
Tens
digit
AI2 curve selection
(1 to 3, as above)
Hundreds
digit
Panel
potentiometer
curve selection (1
to 3, as above)
Units digit, tens digit and hundreds digit of the function code are used to respectively
select the corresponding set curves of analog input AI1, AI2, Panel
potentiometer
3 analog input can respectively select any one of 3 curves.
Curve 1, curve 2 and curve 3 are 2-point curve, they are set in F1 function code.
F1.25
Setting selection for
AI less than minimum
input
Units
digit
Setting
selection
for AI1 less than
minimum input
0x00
☆
The corresponding
minimum input setting
0
0.0%
1
Tens digit
Setting selection
for AI2 less than
minimum input(0
to 1, ditto)
Hundreds
digit
Setting selection
for panel
potentiometer less
than minimum
input(0 to 1, ditto)