Chapter 5 Function parameter
150
MODBUS
protocol
Tens digit
Profibus
PPO1 format
0
PPO2 format
1
PPO3 format
2
PPO5 format
3
F9.06
Communication read
current resolution
0.01A
0
0
☆
0.1A
1
F9.07
Communication card
type
0:Modbus
communication
card
0
0
☆
1:Profibus
communication
card
1
2:Reserved
2
3:CAN bus
communication
card
3
5-2-12.Torque control parameters:FA.00-FA.07
Code
Parameter name
Setting range
Factory
setting
Change
limits
FA.00
Speed/torque control
mode selection
Speed control
0
0
★
Torque control
1
Used to select the inverter control mode: speed control or torque control.
PI9000 multifunction digital terminal has two related functions on torque control:
torque control banned (function 29), and speed control / torque control switching (function
46). The two terminals must use in conjunction with FA.00 so as to switch between speed
control and torque control.
When the speed control / torque control switching terminal is invalid, the control mode
is determined by FA.00, if the terminal is valid, the control manner is equivalent to the
FA.00's value negated.
In any case, when the torque control ban terminal is valid, the inverter is fixed at speed
control mode.
FA.01
Torque setting source
selection
under
torque control mode
Keyboard
setting
(FA.02)
0
0
★
Analog AI1 setting
1
Analog AI2 setting
2
Panel potentiometer
setting
3
High-speed
pulse
setting
4
Communications
5