Chapter 5 Function parameter
115
16
Reserve
17
Frequency source
main set
0
~
max output frequency
F2.09
Maximum output
frequency of high-speed
pulse
0.01kHz to 100.00kHz
50.00kHz
☆
SPB terminal is selected as pulse output, the function code is used to select the
maximum value of output pulse.
F2.10
SPB switching quantity
output delay time
0.0s to 3600.0s
0.0s
☆
F2.11
Relay 1 output delay time 0.0s to 3600.0s
0.0s
☆
F2.12
Expansion DO output
delay time
0.0s to 3600.0s
0.0s
☆
F2.13
SPA output delay time
0.0s to 3600.0s
0.0s
☆
F2.14
Relay 2 output delay time 0.0s to 3600.0s
0.0s
☆
Set the delay time from occurrence to Actual output for output terminal SPA, SPB, relay
1, relay 2 and expansion DO.
F2.15
DO output terminal
active status selection
Units digit
SPB switching
quantity active
status selection
00000
☆
Positive logic
0
Anti-logic
1
Tens digit
Relay 1 terminal
active status
setting (0 to 1,
as above)
Hundreds
digit
Expansion D0
terminal active
status setting (0
to 1, as above)
Thousands
digit
SPA terminal
active status
setting (0 to 1,
as above)
Ten
thousands
digit
Relay 2 terminal
active status
setting (0 to 1,
as above)
To define the output logic for output terminal SPA, SPB, relay 1, relay 2 and expansion
DO .0: positive logic
:
It is active status when the digital output terminal is connected with
the corresponding common terminal, inactive when disconnected; 1: anti-logic
:
It is inactive