15--1
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
Product Specifications
15.1
Model Numbers
The UPS systems are housed in freestanding, cabinets with safety shields behind
the front panels. The UPS systems are available in 50/60 Hz with various output
power ratings. Smaller models within a system may be upgraded in the field to
larger models:
System
Models
Nominal Frequency
Powerware BPIV–15
10 and 15
kVA
50/60 Hz
Powerware BPIV–30
20 and 30
kVA
50/60 Hz
The following sections detail the input, output, environmental, and battery specifications for
the UPS.
15.2
UPS System Input
Operating Input
Voltage
(N10/--15%)
600 VAC for operation from 510 VAC to 660 VAC (50/60 Hz)
480 VAC for operation from 408 VAC to 528 VAC (50/60 Hz)
208 VAC for operation from 177 VAC to 229 VAC (50/60 Hz)
Operating Input
Frequency Range
3 Hz of nominal (50 Hz or 60 Hz)
Operating Input
Current
Refer to Appendix A, Tables A through E, for 10, and 15 kVA
Models and Tables G through K, for 20, 25, and 35 kVA
Models.
Reduced for Generator:
Adjustable
Battery Charge
Current
Battery Charge:
Up to 7 Amperes for 10, and 15 kVA models
Up to 14 Amperes for 20, 25, and 30 kVA models
Input Current
Harmonic Content
10% THD at full load (with input filter option installed)
30% THD at full load (without input filter option installed)
Power Factor
Minimum 0.96
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4
Battery Voltage
288 VDC nominal
(144 cells @2V/cell)