8--6
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
8.4
Options and Accessories
Contact your sales representative for information about any of these available
options:
8.4.1 Remote EMERGENCY POWER OFF
A
REMOTE EMERGENCY POWER OFF
pushbutton is a required option to
provide for situations where you must instantaneously control the UPS output.
The operation of the
REMOTE EMERGENCY POWER OFF
pushbutton is
described in detail in Chapter 10, “UPS Operating Instructions.”
8.4.2 Remote Monitor Panel
An optional
Remote Monitor Panel (RMP)
contains backlit status indicators and a
local horn, allowing the monitoring of the operational status and alarm condition of
the UPS from virtually any location within the facility. You can install multiple RMPs
at remote locations to increase your monitoring capabilities. This option is
described further in Chapter 11, “Using Features.”
8.4.3 Industrial Relay Card
An optional
Industrial Relay Card (IRC)
uses relay contact closures to indicate the
operating status and alarm condition of the UPS system. This interface allows the
monitoring of the operational status of the UPS equipment using the customer’s
monitoring equipment. This option is described further in Chapter 11, “Using
Features.”
8.4.4 Options Cabinet
Input Isolation Transformer
An optional 208/208, 480/208, or 600/208 VAC
input isolation transformer
provides an
isolated input to the UPS rectifier for applications that require a DC link that is not
ground referenced or for applications requiring an input of 480 or 600 VAC. The
transformer is contained in the separate options cabinet.
Bypass Input Isolation Transformer (Dual Input)
An optional 208/208, 480/208, or 600/208 VAC
bypass input isolation transformer
provides an isolated input to the UPS bypass for applications that require an isolated
bypass and an independently derived neutral, or for applications requiring an input of
480 or 600 VAC. The transformer is contained in the separate options cabinet.
Output Isolation Transformer
An optional 208/208 or 208/480 VAC
output isolation transformer
provides an isolated
output to the critical load or for applications that require 480 VAC. The transformer is
contained in a separate options cabinet.
Summary of Contents for BPIV
Page 1: ...www powerware com BPIV INSTALLATION OPERATION MANUAL UPS 10 15 kVA 20 30 kVA...
Page 263: ......
Page 264: ...164201406 Rev C 164201406C...