Electrical input and output
:
Weights and dimensions
:
Environmental and safety
:
Indicators and controls
:
Battery
Table 3. Model List
120V Models
230V Models
UPS Models
PW5119 1K RM
PW5119 1.5K RM
PW5119 2K RM
PW5119 2K RM20R
PW5119 3K RM
PW5119 3K RM20R
PW5119 1Ki RM
PW5119 1.5Ki RM
PW5119 2Ki RM
PW5119 2.4Ki RM
PW5119 3Ki RM
Table 4. Electrical Input
120V Models
230V Models
Nominal Voltage
120V default; 100, 110, 120, 127V selectable
230V default; 208, 220, 230, 240V selectable
Voltage Range
-30% to +20% at full load for nominal voltage; -35% to +20% user-selectable, extended range
Nominal Frequency
60 Hz; 50/60 if 100V or 110V selected
50/60 Hz
Noise Filtering
MOVs and line filter for normal and common mode noise
Connections
1000-1500 VA: 15A, IEC-320 input connector
with detachable 5-15P power cord
2000 VA: 5-20P power cord
3000 VA: 5-30P power cord
1000-2400 VA: 10A, IEC-320 input connector
3000 VA: 16A, IEC-320 input connector