Specifications
31
Powerware
®
5119 Rack Mount User’s Guide
:
www.powerware.com
Table 7. Environmental and Safety
120V Models
230V Models
Operating Temperature
0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Storage Temperature
-20°C to 60°C (-4°F to 140°F)
Relative Humidity
5-95% noncondensing
Operating Altitude
Up to 3,000 meters above sea level
Audible Noise
Less than 45 dBA typical
Surge Suppression
IEEE 587/ANSI C62.41 Category B
Safety Conformance
UL 1778; CSA C22.2, No. 107.1
UL1778; CSA C22.2, No. 107.1;
EN 50091-1 and IEC 60950
Safety Markings
UL, CSA
UL, CSA, CE
EMC
FCC, VCCI
EN 50091-2
Table 8. Indicators and Controls
Serial Communication
Intelligent serial communication to provide alarms with history, measured parameters, self-test,
and many other features; contact your authorized dealer for UPS/computer communication
software options
Interface
Ergonomic Indicators: Wiring Fault, Battery Service, Communication, Operation, System Normal
Bar Graphs: Input Level, Battery Charge Level, % Load
Contact Closures
AC Input Failure, Low Battery
Table 9. Battery
Configuration
Internal batteries
Voltage
1000-1500 VA: 24 Vdc
2000-3000 VA: 48 Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Advanced charging for faster recovery; approximately 4 hours to 90% usable capacity at nominal
line and no supplementary power supply load
Monitoring
Advanced monitoring for earlier failure detection and warning