Installation
4
Powerware
®
5119 Rack Mount User’s Guide
:
www.powerware.com
W A R N I N G
:
This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
:
Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
:
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants.
Ambient temperature must not exceed 40
C (104
F). Do not operate near water
or excessive humidity (95% max).
:
The sum of earth leakage current from the load connected to the UPS must not
exceed 1.5 mA.
Mounting the UPS in a Rack
The UPS fits in a 19-inch rack. Follow the steps below to install the UPS
in the rack.
C A U T I O N
The UPS is heavy (132 lb/60 kg). A minimum of two people are required to lift the
UPS into the rack.
NOTE
Disconnect all cables from the UPS before continuing. Remove all self-
adhesive pads from the underside of the unit if already fitted.
1.
Place the UPS on a flat, stable surface with the front of the UPS
facing toward you.
2.
If the mounting brackets are not already installed, position the
mounting bracket over the mounting holes on one side of the
unit and secure with the provided screws (see Figure 2).
If the mounting handles are not already installed, position the
mounting handle over the bracket and secure with the
provided screws (see Figure 3).
3.
Repeat Step 2 for the other side of the UPS.
4.
Using at least two people, lift the UPS and slide it into the rack.
5.
Secure the UPS by screwing the mounting angles to the rack
face (screws not provided). The UPS is now secured in the rack.