Configuration
19
Powerware
®
5119 Rack Mount User’s Guide
:
www.powerware.com
Table 1. Configuration Mode LEDs and Options
LED
Option
Power On
Indicator
Explanation
120/230V Nominal
Input Voltage
ON (default)
Nominal input voltage on low voltage models is 120V and on high voltage
models is 230V; all other nominal input voltages are disabled.
OFF*
120/230V is disabled; one of the other input voltage options is selected.
*This is the default for models that are factory-configured for 100V or 208V (see
the rating on the UPS rear panel).
110/220V Nominal
Input Voltage
ON
Selecting this option changes the nominal input voltage on low voltage models
to 110V and to 220V for high voltage models.
OFF (default)
110/220V is disabled; one of the other input voltage options is selected.
127/240V Nominal
Input Voltage
ON
Selecting this option changes the nominal input voltage on low voltage models
to 127V and to 240V for high voltage models.
OFF (default)
127/240V is disabled; one of the other input voltage options is selected.
120/230V Extended
Voltage Mode
ON
The UPS accepts an input voltage within -35% to +20% of 120V or 230V
nominal input voltage before switching to battery.
OFF (default)
The UPS accepts an input voltage within -30% to +20% of 120V or 230V
nominal input voltage before switching to battery.
Site Wiring Fault
Alarm
ON (default)
Alarm sounds when the polarity of the outlet is reversed or the ground
connection is missing; have a qualified electrician repair the outlet wiring.
OFF*
Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground
connection is missing.
*Site Wiring Fault is not available for 100V or 208V models; OFF is the default.
Low Battery Alarm
ON (default)
Alarm sounds approximately 3 minutes before battery shutdown.
OFF
Alarm sounds approximately 5 minutes before battery shutdown.